2.1.2.2
Technical data
Technical data
Task within the EtherCAT system
Transmission medium
Cable length between two Bus Couplers max. 300 m
Protocol
Data transfer rates
Configuration
Bus connection
Delay
Power supply
Current consumption
General data
Dimensions (W x H x D)
Weight
Permissible ambient temperature range
during operation
Permissible ambient temperature range
during storage
Permissible relative humidity
Mounting [} 58]
Vibration/shock resistance
EMC immunity/emission
Protection class
Installation position
Approvals / markings
*) Real applicable approvals/markings see type plate on the side (product marking).
EK112x, EK15xx
EK1121-0010
coupling of 100BASE-TX EtherCAT networks
Ethernet/EtherCAT cable (copper, min. Cat. 5, 4-wire, AWG22),
shielded
EtherCAT
100 Mbit/s
no address and configuration settings required
1 x RJ45
typ. 1 µs
from E-bus
typ. 160 mA
EK1121-0010
approx. 26 mm x 100 mm x 52 mm (width aligned: 23 mm)
approx. 65 g
0°C ... +55°C
-25°C ... + 85°C
95%, no condensation
on 35 mm mounting rail conforms to EN 60715
conforms to EN 60068-2-6 / EN 60068-2-27
conforms to EN 61000-6-2 / EN 61000-6-4
IP20
variable
CE, cULus [} 63]
Version: 3.6
Product overview
23