<Multiple Unit Installation>
Min. 25
3.Walls in 4 Directions
<Single Unit Installation>
<Multiple Unit Installation>
●
Keep the upper side open.
●
The front side should be less than 1,500mm; air inlet side should be less than 500mm; other sides are no limits.
●
If the heights are beyond the limits, add h1/2mm and h2/2mm on the front side and air inlet side respectively.
●
For the multiple installation, one group allows 6 outdoor units(max.). The required space between each set is at
least 1m.
●
The walls should be partially open if the unit is surrounded by walls in four directions.
Note:If the distance between unit and obstacles/ceilings is less than 1,500mm or the space is closed, set up the
duct on the air outlet side to prevent the return air.
Min. 25
7
Unit:mm