Hitachi RAM-160FSPH Instruction Manual

Inverter-driven multi-split system air conditioning

Advertisement

Quick Links

Installation Manual
Inverter-Driven
Multi-Split System
Air Conditioning
Models:
RAM-160FSPH
RAM-160FSPHB
RAM-140FSPH
RAM-140FSPHB
RAM-125FSPH
RAM-125FSPHB
․Before installation, please read this manual carefully and keep it properly.
․Make sure to hand over this manual to workers of the next stage and finally let the customer keep it.
(Transportation and Handling) → (Refrigerant Piping) → (Electrical Wiring) → (Test Run) → (Customer)
Important Notice
․This Air Conditioner has been designed for common air conditioning for people. Do not apply to other purposes
such as for food, animals, plants, high precision machines or work of art.
․Do not install the unit in the following places. It may cause fire, deformation, corrosion or failure.
o Places where is filled with mineral oil mist or oil spray (including machinery oil) or vapor is produced.
o Places where is filled with sulfurous gas such as hot spring area.
․Do not install the unit in the following places, it may cause corrosion.
o Places where strong salty wind blows such as coast regions.
o An acid or alkaline environment.
․Pay attention to the following situations when the unit is installed in a hospital or other facilities where
o
electromagnetic wave is radiated from medical equipment.
o Do not install the unit where the electromagnetic wave is directly radiated to the electrical box, remote
control cable or remote-control switch
o o To avoid the influence of electromagnetic waves via air, wave generating machines such as radio, medical
equipment must be kept at least 3 meters form air conditioner.
o
․Do not install the unit in the place where wind directly blows on animals or plants. It could adversely affect them.
․Using wireless remote controller, the receiver may fail to receive signals due to effect of the lighting equipment.
Therefore, keep the receiver away from the lighting equipment more than 1 meter as possible
INDEX Table of Contents
2
Safety Precautions
3
Transportation and Handling
5
Installation Procedure
7
Refrigerant Piping Works
14
Electrical Wiring
15
DSW Dip Switch Setting
17
Test Run
19
Alarm Code
1

Advertisement

Table of Contents
loading

Summary of Contents for Hitachi RAM-160FSPH

  • Page 1 Installation Manual Inverter-Driven Multi-Split System Air Conditioning INDEX Table of Contents Models: Safety Precautions RAM-160FSPH Transportation and Handling RAM-160FSPHB Installation Procedure Refrigerant Piping Works RAM-140FSPH Electrical Wiring RAM-140FSPHB DSW Dip Switch Setting Test Run RAM-125FSPH Alarm Code RAM-125FSPHB ․Before installation, please read this manual carefully and keep it properly.
  • Page 2: Safety Precautions

    1.Safety Precautions ․Before installation, carefully read this section in order to install it correctly. ․This manual contains “⚠Danger” . This symbol indicates a hazardous situation which if installed incorrectly It may result in death or serious injury. Therefore, make sure to observe important message of safety. ․While checking any abnormality during test run after installation, explain to costumer the correct methods of Usage and maintenance according to the User’s Manual.
  • Page 3: Transportation And Handling

    2. Transportation and Handling (1) When transporting the outdoor unit, observe the following item. Please transport the unit to the installation location under packed condition. ●Hanging Method without Packing: ●Hanging Method with Packing: Hang the unit with two ropes. Thickness of Hang the unit with two ropes plywood or cardboard must...
  • Page 4 No interchangeability is available due to higher pressure when Vacuum compared with R22. Manifold Valve Pumping; ● ■ R410A connection diameter:1/2 UNF Vacuum holding; R407C connection diameter:7/16 UNF refrigerant ◎<Do not use current ones (R22) to the different charging and Charging Hose refrigerant>;...
  • Page 5 Please refer to the table below to select the quantity and capacity of Outdoor Units and Indoor Units. Indoor Unit Outdoor Unit Model Combined Capacity Ratio Maximum quantity of combined units RAM-160FSPH(B) RAM-140FSPH(B) 50~130% (Outdoor unit capacity) RAM-125FSPH(B) (6) Cooling Operating Instructions The same refrigerant system of indoor unit, the cooling shall be operated.
  • Page 6 (When installing under roofs where condensate drips, this may wet the floor to cause fall in winter.) Also, using central draining pipes is easier. (In frigid zones, condensate from defrosting may freeze in winter, do not use central draining pipes.) 4.Provide a foundation so that the entire footing of the outdoor unit can be mounted on the foundation.
  • Page 7: Refrigerant Piping Works

    4. Refrigerant Piping Works (1) Piping Work 1)Refrigerant Pipe Selection ①Please prepare the refrigerant pipe by field supplied. ②Select clean copper pipes. Make sure there is no dust and moisture inside of the pipes. ●Cut off the refrigerant piping, use the pipe cutter. Blow the inside of the pipes with nitrogen or dry air, to remove any dust or foreign materials before connecting pipes.
  • Page 8 Piping Connection Example: These figures show example of 6 indoor units combined with 1 outdoor unit. The refrigerant pipes are shown as single line in the diagrams. However, liquid line piping and gas piping are required in the field piping work. Total piping Length:Lt+ L0 + L1+ L2+ L3+ L4 Within 300m Maximum Piping...
  • Page 9 (2) Refrigerant Pipe Diameter  Outdoor Unit  Indoor Unit Pipe Diameter(mm) Pipe Diameter(mm) Horsepower Gas side Liquid Side Gas Side Liquid Side 0.8~6.0HP Please select according to the Φ15.88 Φ9.53 indoor model type and grade 22~160 Level The multi-kit pipe, which is connected to the indoor unit, be sure to use an optional part of the multi-kit pipe set, in order to prevent the uneven distribution of the refrigerant and causing the unit’s capacity reduction.
  • Page 10 (4) Piping Direction...
  • Page 11 (5) Piping Connection, Installation 1)Check if the stop valve of outdoor unit is closed. 2)Please connect the piping between indoor and outdoor unit. When tightening the joints of piping, in the inside and outside of flare piping, please coated with a layer of refrigerant oil [Field Supplied (Idemitsu Kosan Co., Ltd. Synthetic Oil “FVC68D”)], and in accordance with the provisions of tightening torque with double spanner to tighten.
  • Page 12 Please implement vacuum drying determination, to confirm whether water exist within the system. If moisture is present, please extend the vacuum time or installation the drying filter until no moisture is present within the system. Be sure to do this work, otherwise in the future the unit could easily lead to failure, and difficult to handle. ※Note: 1.When remove the spindle calve cap of stop valve, there may be slight refrigerant leakage sound is normal.
  • Page 13 (9) Precaution for Refrigerant Leakage In the room where the air conditioner is installed, in case of refrigerant leakage, the concentration of refrigerant should not exceed the limit ●This product uses non-flammable, non-toxic safe refrigerant R410A, in case the refrigerant of the indoor unit leaks and fills the whole room, there will be a danger of suffocation.
  • Page 14: Electrical Wiring

    5. Electrical Wiring (1) Electrical Work Please entrust qualified distributors, and according to relevant national laws and regulations for construction. In electrical wiring, please use 3-phase/single-phase 220V ways. ELB (Leakage Power Switch Power Circuit Breaker) Earth Transmission PROJECT Maximu Supply Wire Cable Size Rated...
  • Page 15 (2) Wiring Connection Port The indoor unit wiring connection port, please connect the wiring according to the indoor unit installation manual instruction. RAM-125,140,160FSPH RAM-125,140,160FSPHBB Noise Filter (Gray) Ground Wire (3) Indoor unit and outdoor unit electrical wiring 1) 1. Please follow the electrical wiring instructions in connecting the power source cables of indoor and outdoor unit at page 14.
  • Page 16 (2) Other Settings: ●RAM-125,140,160FSPH ●RAM-125,140,160FSPHBB...
  • Page 17 7. Test Run (1) Test Run Caution before test running 1) Please use the 500V electrical resistance tester to check the electrical parts between terminals and earth, the electrical resistance must be more than 1MΩ or below, please check the electrical resistance once again. 2) Make sure that the stop valves of the outdoor unit are fully opened, and then start the system.
  • Page 18 Test Run and Maintenance Record MODEL: SERIAL. No. COMPRESSOR MFG. No. DATE: CUSTOMER'S NAME AND ADDRESS: 1. Is the rotation direction of the indoor coil fan correct? 2. Is the rotation direction of the outdoor coil fan correct? 3. Are there any abnormal compressor sounds? 4.
  • Page 19: Alarm Code

    Alarm Code Code Distinction Content of Abnormality Leading Cause Indoor Unit Activation of Protection Device (Float Activation of Float Switch (High water Level Drain Pan, Abnormality of Indoor Unit Switch) Drainpipe, Float Switch or Drain Pan) Activation of High Pressure Switch (4.15MPa); Air Conditioner Outdoor Outdoor Unit Activation of Protection Device Outdoor Unit Unit Fan Motor Lock.
  • Page 20 66MP1560-A1 Printed in Philippines...