Ground Fault Interrupter Activates When Drive is Running
Cause
The output of the drive is a series of high
frequency pulses (PWM), so there is a
certain amount of leakage current. This
may cause the ground fault interrupter to
operate and cut off the drive input power.
YASKAWA ELECTRIC TOEP C710606 25D YASKAWA AC Drive J1000 Installation & Start-Up Manual
5.8 Troubleshooting without Fault Display
Possible Solutions
• Change to a ground fault interrupter with a higher leakage current
detection level (such as, a sensitivity current of 200 mA or greater per
Unit, with an operating time of 0.1 s or more), or one that incorporates
high-frequency corrective actions.
• Change the Carrier Frequency Selection (C6-02) to lower the carrier
frequency.
Note: Leakage current increases in proportion to cable length.