Installation and Connection
3
3.3 INSTALLATION ACCORDING TO THE EUROPEAN DIRECTIVE OF
ELECTROMAGNETIC COMPATIBILITY
The CFW-11 RB converters, when properly installed, meet the requirements of the electromagnetic compatibility
directive "EMC Directive 2004 / 108 / EC".

3.3.1 Conformal Installation

For the conformal installation use:
1. Input filter and RFI in order to comply with the conducted emission levels C3 categorie.
2. Shielded control cables, keeping them separate from the other cables as described at
Connections on page
3. Converter grounding according to the instructions at
4. Instruction for conformal installations applicable to converters controlling motors.
3-34 | CFW-11 RB
General
Enable
Figure 3.29: XC1 wiring for control connection 1
3-30.
XC1 Connector
7
AO1
8
AGND (24 V)
9
AO2
10
AGND (24 V)
11
DGND
(*)
12
COM
13
24 Vcc
14
COM
15
DI1
16
DI2
17
DI3
18
DI4
19
DI5
20
DI6
21
NF1
DO1
22
C1
(RL1)
23
NA1
24
NF2
DO2
25
C2
(RL2)
26
NA2
27
NF3
DO3
28
C3
(RL3)
29
NA3
Item 3.2.5 Grounding Connections on page
Item 3.2.8 Control
3-26.