Electronics/General Data; Codes And Standards - WEG CFW-11 RB User Manual

Regenerative frequency converter
Table of Contents

Advertisement

8.2 ELECTRONICS/GENERAL DATA

Control
Method
Inputs
Digital
(CC11 RB board)
Outputs
Analog
(CC11 RB board)
Relay
Safety
Protection
Integral
Standard
Keypad (HMI)
Keypad
Enclosure
IP20
IP00
PC Connection
USB
for Converter
Connector
Programming

8.2.1 Codes and Standards

Safety Standards
Electromagnetic Compatibility
(EMC)
Mechanical Standards
Type of control
- Vector Control
PWM SVM (Space Vector Modulation)
Current, DC link voltage and reactive regulators
6 isolated differential inputs, 24 Vdc, programmable functions
2 isolated analog outputs, (0 to 10) V, RL ≥ 10 kΩ (maximum load), 0 to 20 mA /
4 to 20 mA (RL ≤ 500 Ω) resolution: 11 bits, programmable functions
3 relay outputs with NO/NC contacts, 240 Vac, 1 A, programmable functions
Input Overcurrent/Short-circuit
Under/Overvoltage
Phase loss
Overtemperature
IGBTs overload
External Fault/Alarm
CPU or memory fault
DC link phase-ground short-circuit
4 keys: active : Up Arrow, Down Arrow, Right Soft Key and Left Soft Key.
disabled: General Enable/Disable, Direction of Rotation, JOG, Local/Remote
Graphical LCD display
View/edition of all parameters
Indication accuracy:
- current: 5 % of the rated current
Possibility of remote assembly
Frame size E
Frames sizes F and G
USB standard Rev. 2.0 (basic speed)
Type B (device) USB plug
Interconnection cable: standard host/device shielded USB cable
UL 508C - Power conversion equipment
UL 840 - Insulation coordination including clearances and creepage distances for electrical
equipment
EN61800-5-1 - Safety requirements electrical, thermal and energy
EN 50178 - Electronic equipment for use in power installations
EN 60146 (IEC 146) - Semiconductor converters
EN 61800-2 - Adjustable speed electrical power drive systems - Part 2: General requirements -
Rating specifications for low voltage adjustable frequency AC power drive systems
EN 61800-3 - Adjustable speed electrical power drive systems - Part 3: EMC product standard
including specific test methods
EN 55011 - Limits and methods of measurement of radio disturbance characteristics of
industrial, scientific and medical (ISM) radio-frequency equipment
CISPR 11 - Industrial, scientific and medical (ISM) radio-frequency equipment -
Electromagnetic disturbance characteristics - Limits and methods of measurement
EN 61000-4-2 - Electromagnetic compatibility (EMC) - Part 4: Testing and measurement
techniques - Section 2: Electrostatic discharge immunity test
EN 61000-4-3 - Electromagnetic compatibility (EMC) - Part 4: Testing and measurement
techniques - Section 3: Radiated, radio-frequency, electromagnetic field immunity test
EN 61000-4-4 - Electromagnetic compatibility (EMC) - Part 4: Testing and measurement
techniques - Section 4: Electrical fast transient/burst immunity test
EN 61000-4-5 - Electromagnetic compatibility (EMC) - Part 4: Testing and measurement
techniques - Section 5: Surge immunity test
EN 61000-4-6 - Electromagnetic compatibility (EMC)- Part 4: Testing and measurement
techniques - Section 6: Immunity to conducted disturbances, induced by radio-frequency
fields
EN 60529 - Degrees of protection provided by enclosures (IP code)
UL 50 - Enclosures for electrical equipment
Technical Specifications