3.1.3 Cabinet Mounting

There are two possibilities for mounting the converter: surface mounting or flange mounting (the heatsink is
mounted outside the cabinet and the cooling air of the power module is kept outside the enclosure). The following
information shall be considered in these cases:
Surface Assembly:
Provide adequate exhaustion so that the internal cabinet temperature is kept within the allowable operating
range of the converter.
The power dissipated by the converter at its rated condition, as specified in
8.4 on page 8-5
"Dissipated power in Watts - Surface mounting".
The cooling air flow requirements, as shown in
The position and diameter of the mounting holes, according to
page
3-4.
Flange Assembly:
Frame Size E:
The power specified in
Table 8.1 on page 8-2
mounting" will be dissipated inside the cabinet. The remaining losses (power module) will be dissipated through
the vents.
The converter securing supports (position H of
Figure 2.2 on page
2-5) must be removed and repositioned according to the
Figure 3.6 on page
3-8.
The portion of the converter that is located outside the cabinet is rated IP54. Provide an adequate gasket for
the cabinet opening to ensure that the enclosure rating is maintained. Example: silicone gasket.
Mounting surface opening dimensions and position/diameter of the mounting holes, as shown in
on page 3-3
Frame Sizes F and G:
ATTENTION!
The part of the converter that stays outside the cabinet is rated IP20.
The power specified in
- Flange mounting" will be dissipated inside the cabinet. The other losses (power modules) will be dissipated
at the external ventilation duct.
The converter mounting supports and the hoisting eyes must be removed. Refer to the
2-6, positions H and I.
Dimensions of the flange-mounting opening and the diameters of the securing holes must be according to
the
Figure 3.2 on page
3-4.
Frame Size
Table 3.1 on page
to
Table 8.4 on page 8-5
Figure 2.2 on page
Table 8.1 on page 8-2
to
Table 8.4 on page 8-5
Table 3.1: Minimum required cabinet cooling air flow
CFM
E
265
F
460
G
680
Installation and Connection
Table 8.1 on page 8-2
3-7.
Figure 3.1 on page 3-3
"Dissipated power in Watts - flange
2-5) and the hoisting eyes (position I of
Figure 3.5 on page 3-8
under "Dissipated power in Watts
I/s
m³/min
125
7,5
217
13
321
19,3
to
Table
and
Figure 3.2 on
3
and
Figure 3.1
Figure 2.3 on page
CFW-11 RB | 3-7