Installation and Connection

3.2.8 Control Connections

The control connections (analog inputs/outputs, and digital inputs/outputs) must be made at the electronic control
board CC11 RB terminal strip XC1.
Functions and typical connections are presented at
volt
amp
3
3-30 | CFW-11 RB
XC1
Factory Default
Connector
Function
7
AO1
Analog output 1:
DC Link voltage
8
AGND
Reference (0 V) for the
(24 V)
analog outputs
9
AO2
Analog output 2:
AC Current
10
AGND
Reference (0 V) for the
(24 V)
analog outputs
11 DGND* 24 Vdc power supply
12
COM
Digital inputs common
point connection
13
24 Vcc 24 Vdc power supply
14
COM
Digital inputs common
point connection
15
DI1
Digital input 1:
General enable
16
DI2
Digital input 2:
No function
17
DI3
Digital input 3:
No function
18
DI4
Digital input 4:
No function
19
DI5
Digital input 5:
No function
20
DI6
Digital input 6:
No function
21
NF1
Digital output 1 DO1
(RL1): Pre-charge OK
22
C1
23
NA1
24
NF2
Digital output 2 DO2
(RL2): RUN
25
C2
26
NA2
27
NF3
Digital output 3 DO3 (RL3):
No fault
28
C3
29
NA3
a) Digital inputs as active high
Figure 3.25 on page
3-31.
Specifications
Galvanic Isolation
Resolution: 11 bits
Signal: 0 to 10 V (R
≥ 10 kΩ) / 0 to 20 mA / 4 to 20 mA (R
L
Protected against short-circuit
Connected to the ground (frame) through impedance: 940 Ω resistor
in parallel with a 22 nF capacitor
Galvanic Isolation
Resolution: 11 bits
Signal: 0 to 10 V (R
≥ 10 kΩ) / 0 to 20 mA / 4 to 20 mA (R
L
Protected against short-circuit
Connected to the ground (frame) through impedance: 940 Ω resistor
in parallel with a 22 nF capacitor
Connected to the ground (frame) through impedance: 940 Ω resistor
in parallel with a 22 nF capacitor
24 Vdc power supply, ±8 %
Capacity: 500 mA
6 isolated digital inputs
High level ≥ 18 V
Low level ≤ 3 V
Maximum input voltage = 30 V
Input current: 11 mA @ 24 Vdc
Contact rating:
Maximum voltage: 240 Vac
Maximum current: 1 A
NC - normally closed contact
C - common
NO - normally open contact
≤ 500 Ω)
L
≤ 500 Ω)
L