XC1
Connector
7
AO1
volt
8
AGND
(24 V)
9
AO2
amp
10
AGND
(24 V)
11
DGND* Reference (0 V) for
12
COM
13
24 Vcc
14
COM
15
DI1
16
DI2
17
DI3
18
DI4
19
DI5
20
DI6
21
NF1
22
C1
23
NA1
24
NF2
25
C2
26
NA2
27
NF3
28
C3
29
NA3
NOTE!
Remove the jumper between XC1:11 and 12 and install it between XC1:12 and 13 to use the digital
inputs as active low.
Factory Default
Function
Analog output 1:
Galvanic Isolation
DC Link voltage
Resolution: 11 bits.
Signal: 0 to 10 V (R
Protected against short-circuit
Reference (0 V) for
Connected to the ground (frame) through impedance: 940 Ω resistor
the analog outputs
in parallel with a 22 nF capacitor
Analog output 2:
Galvanic Isolation
AC Current
Resolution: 11 bits.
Signal: 0 to 10 V (R
Protected against short-circuit
Reference (0 V) for
Connected to the ground (frame) through impedance: 940 Ω resistor
the analog outputs
in parallel with a 22 nF capacitor
Connected to the ground (frame) through impedance: 940 Ω resistor
the 24 Vdc power
in parallel with a 22 nF capacitor
supply
Digital inputs
common point
connection
24 Vdc power supply 24 Vdc power supply, ±8 %.
Capacity: 500 mA
Digital inputs
common point
connection
Digital input 1:
6 isolated digital inputs
General enable
High level ≥ 18 V
Low level ≤ 3 V
Digital input 2:
Maximum input voltage = 30 V
No function
Input current: 11 mA @ 24 Vdc
Digital input 3:
No function
Digital input 4:
No function
Digital input 5:
No function
Digital input 6:
No function
Digital output 1 DO1
Contact rating:
(RL1): Pre-charge OK
Maximum voltage: 240 Vac
Maximum current: 1 A
NC - normally closed contact
Digital output 2 DO2
C - common.
(RL2): RUN
NO - normally open contact
Digital output 3 DO3
(RL3): No fault
b) Digital inputs as active low
Figure 3.25: (a) and (b) XC1 connector signals
Installation and Connection
Specifications
≥ 10 kΩ) / 0 to 20 mA / 4 to 20 mA (R
L
≥ 10 kΩ) / 0 to 20 mA / 4 a 20 mA (R
L
≤ 500 Ω)
L
≤ 500 Ω)
L
3
CFW-11 RB | 3-31