PARAMETER SETTING
Press
for 5 sec
pass
Press
key
SET
Press
key
SET
Press
key
SET
eNBL
Press
key
SET
Press
key
SET
eNBL
Press
key
SET
Press
key
SET
eNBL
Press
key
SET
Press
key
SET
eNBL
Press
key
SET
IF
1Ø-2W
Press
key
SET
Selected
eNBL
Press
key
SET
Press
key
SET
eNBL
Press
key
SET
IF
1Ø-2W
Press
key
SET
Selected
eNBL
Press
key
SET
Password
Enter Password 11
11
Over Voltage
OV
(Enable/Disable)
UV
(Under Voltage)
(Enable/Disable)
OF
(Over Frequency)
(Enable/Disable)
UF
(Under Frequency)
(Enable/Disable)
as
(Asymmetry)
(Enable/Disable)
pL
(Phase loss)
(Enable/Disable)
ps
(Phase Sequence)
(Enable/Disable)
key for save & exit
SET
Password 11 : To Enable / Disable parameter
(Over Voltage, Under Voltage,over
Frequency,Under Frequency,
Asymmetry,Phass loss, Phase
sequence)
Password 37 : To set Power on delay time, Trip delay
Time,Relay Fault Mode, Reset mode,
network selectiom
Relay Settings
Press
SET
Press
SET
If Over
Voltage
Press
is Disable
SET
Press
SET
If Under
Voltage
Press
SET
is Disable
Press
SET
If Over
Press
SET
Frequency
is Disable
Press
SET
If Under
Frequency
Press
SET
is Disable
Press
key
SET
If
Asymmetry
is Disable
Press
or
SET
IF 1Ø-2W
Selected
Press
Press
key
SET
for 5 sec
pasS
Password
key
Enter Password 73
73
key
If over voltage is enable
OVR1
(Over Voltage Of Relay)
key
(Over Voltage value)
280
(
85-550V For 3Ø-3W )
(50-330V For 3Ø-4W/1Ø-2W
key
If under voltage is enable
uVR1
(Under Voltage of Relay)
key
210
(Under Voltage Value)
(
85-520V For 3Ø-3W )
(50-300V For 3Ø-4W/1Ø-2W
key
If Over Frequency is Enable
OFR1
(Over Frequency of Relay)
key
550
(Over Frequency Value)
(45.0-65.0 Hz)
key
If Under Frequency is Enable
UFR1
(Under Frequency Of Relay)
key
4SS
(Under Frequency value)
(45.0-65.0 Hz)
IF 3Ø-4W/3Ø-3W Selected
If Asymmetry is Enable
ASR1
(Asymmetry Of Relay)
key
(Asymmetry Percentage)
20
(2 - 30%)
key for save & exit
SET
)
)
Need help?