Other settings are possible taking into account the following rules:
• above 70°C disinfection lasts 30 minutes
• between 65° and 70°C disinfection lasts 60 minutes;
• between 60° and 65°C disinfection lasts 120 minutes;
• between 57.5° and 60°C disinfection lasts 180 minutes;
• between 55°C and 57.5°C disinfection lasts 240 minutes;
The controller doesn't signal the execution of the Anti-Legionella function.
The regulator performs a check according to the preset parameters and exits the Anti-Legionella function after a timeout of
5 hours.
During the Anti-Legionella function, the cooling and heating requirements of the system are not fulfilled.