PT4
PT5
PT6
PT8
Output status
PP1
PV1/PP2
PP3
PR1/PP5
EXTA "ON-OFF"
EXTB "SIL"
AUX1
Tout/PWM
Installer menu
Installer parameters (PF)
ECE
ESL
ESH
ESP
Views: domestic hot water storage temperature
#
Display: water exchanger outlet temperature
#
Display: water exchanger inlet temperature
#
Views: external air temperature
#
Indicate: primary pump
#
Indica: sanitary three-way valve
#
Indicate: secondary pump
#
Indicates: auxiliary resistance
#
Indicates: Outdoor unit call
#
Indicates: silent function activation
#
Indicates: alarm output
#
Indicates: temperature probe malfunction
#
Enable: SUMMER function (Cooling)
#
NO: disabled
#
YES: enabled (default)
#
Set: minimum SUMMER setpoint (Cooling)
#
Units of measure: °C
#
Minimum: 7
#
Maximum: 40
#
Setting: 10
#
Set: maximum SUMMER setpoint (Cooling)
#
Units of measure: °C
#
Minimum: 7
#
Maximum: 40
#
Setting: 20
#
Set: SUMMER setpoint (Cooling)
#
Units of measure: °C
#
Minimum: 7
#
Maximum: 40
#
Setting: 12
#