TESY MultiThermica User's And Installer's Manual page 20

Residential heat pump control panel
Table of Contents

Advertisement

MEnU STRUCTURE
20
HTO
Set: resistance timeout
#
Unit of measurement: minutes
#
Minimum: 0
#
Maximum: 240
#
Setting: 20
#
AHI
Set: high temperature alarm PT1 probes
#
Units of measure: °C
#
Minimum: 20
#
Maximum: 95
#
Setting: 80
#
ALO
Set: alarm low temperature probes PT1
#
Units of measure: °C
#
Minimum: 3
#
Maximum: 30
#
Setting: 5
#
PMS
Enable: operation mode
#
CON: continuous
#
NOR: on request
#
TIM: Energy Saving (Default)
#
PRT
Set: Pump OFF time energy saving cycle
#
Unit of measurement: min
#
Minimum: 1
#
Maximum: 30
#
Setting: 2
#
PST
Set: Pump OFF time energy saving cycle
#
Unit of measurement: min
#
Minimum: 10
#
Maximum: 240
#
Setting: 15
#
PRD
Set: Pump switch-off delay
#
Unit of measurement: min
#
Minimum: 1
#
Maximum: 30
#
Setting: 2
#
CLI
Enable: climatic and PT8
#
NO: disabled
#
YES: enabled (default)
#
OTH
Set: maximum outside temperature for climate control
#
Units of measure: °C
#
Minimum: -30
#
Maximum: 40
#
Setting: 15
#
OTL
Set: minimum outside temperature for climate control
#
Units of measure: °C
#
Minimum: -30
#
Maximum: 40
#
Setting: -5
#

Advertisement

Table of Contents
loading

This manual is also suitable for:

Multithermica maxMultithermica rhp 9 1p he6 nvMultithermica rhp 7 1p he6 nvMultithermica rhp 5 1p he6 nvMultithermica rhp 12 1p he6 nvMultithermica rhp 18 3p he6 nv ... Show all

Table of Contents