Figure 6.14 Fan module
4. Make note of the fan module's orientation and lift the fan module up and out of
the enclosure.
Fan module removal is complete. Install the replacement fan module.
Installing a Fan Module
1. Ensure the necessary service action preparation was performed as required to
install a fan module, which includes:
a. "Enclosure Extension" section.
b. "Removing the Enclosure's Top Cover" section.
2. Become familiar with the edge fingers on the bottom of the fan module and the
connector in the fan module slot of the enclosure.
3. Insert the new fan module in the same orientation as the removed fan module,
with the fan module board facing the rear of the enclosure.
4. Press down on the fan module firmly to secure it in place. The fan module is
not fully seated until the release tabs audibly click into place.
5. Follow the instructions provided to complete a service action, which include:
a. "Returning the Top Cover to the Enclosure" section.
b. "Returning the Enclosure to the Rack" section.
Fan module replacement is complete. The fan module LED and the cooling group
LEDs on the front operator panel return to normal status.
I/O MODULES
IOMs are hot-swappable and may be replaced while the system is in operation.
Replacement should be made within five (5) minutes to ensure proper system
cooling. To remove and install an IOM, use the following procedures.