3.6.2 Repair procedures

To correct the wiring from the indoor unit power supply terminal to the indoor unit main PCB
To remove the indoor unit main PCB
ATXP20~35 + FTXP20~71 + ARXP20~35 + RXP20~71
Split Comfora R32
ESIE18-01E – 2023.01
Blown fuse on the indoor unit main
PCB?
No
After all checking procedures listed above have been performed:
Is the problem solved?
Yes
No
Prerequisite: Stop the unit operation via the user interface.
Prerequisite: Turn OFF the respective circuit breaker.
Prerequisite: Remove the required plate work, see
1 Correct the wiring from the indoor unit power supply terminal to the PCB, see
"6.2 Wiring
diagram" [
Is the problem solved?
Yes
No
Prerequisite: Stop the unit operation via the user interface.
Prerequisite: Turn OFF the respective circuit breaker.
Prerequisite: Remove the required plate work, see
1 Disconnect all connectors from the indoor unit main PCB.
2 Carefully pull the indoor unit main PCB from the PCB supports.
Action
Return to
procedures" [
main PCB and continue with the next
procedure.
Action
No further actions required.
Return to the troubleshooting of the
specific error and continue with the
next procedure.
4
 159].
Action
No further actions required.
Return to
procedures" [
main PCB and continue with the next
procedure.
3
Components
|
"3.6.1 Checking
4
 78] of the indoor unit
4
"3.9 Plate
work" [
 111].
"3.6.1 Checking
4
 78] of the indoor unit
4
"3.9 Plate
work" [
 111].
Service manual