Daikin FTXP25N5V1B9 Installer's Reference Manual

Daikin FTXP25N5V1B9 Installer's Reference Manual

Hide thumbs Also See for FTXP25N5V1B9:
Table of Contents

Advertisement

Quick Links

FTXP20N5V1B9
FTXP25N5V1B9
FTXP35N5V1B9
ATXP20N5V1B9
ATXP25N5V1B9
ATXP35N5V1B9
Installer reference guide
Split system air conditioners

Advertisement

Table of Contents
loading

Summary of Contents for Daikin FTXP25N5V1B9

  • Page 1 Installer reference guide Split system air conditioners FTXP20N5V1B9 FTXP25N5V1B9 FTXP35N5V1B9 ATXP20N5V1B9 ATXP25N5V1B9 ATXP35N5V1B9...
  • Page 2: Table Of Contents

    Table of contents Table of contents 1 About the documentation About this document ..............................2 General safety precautions About the documentation .............................. 2.1.1 Meaning of warnings and symbols ........................ For the installer ................................2.2.1 General ................................2.2.2 Installation site ............................... 2.2.3 Refrigerant —...
  • Page 3 Table of contents 8.2.5 To connect the electrical wiring to the indoor unit..................41 8.2.6 To connect to an HA system (Wired remote controller, Central remote controller, wireles adaptor, etc.) ................................. 42 9 Finishing the indoor unit installation To insulate the drain piping, refrigerant piping and interconnection cable..............44 To pass the pipes through the wall hole ........................
  • Page 4: About The Documentation

    The original instructions are written in English. All other languages are translations of the original instructions. Technical engineering data ▪ A subset of the latest technical data is available on the regional Daikin website (publicly accessible). ▪ The full set of latest technical data is available on the Daikin Business Portal (authentication required).
  • Page 5: General Safety Precautions

    General safety precautions 2 General safety precautions 2.1 About the documentation ▪ The original instructions are written in English. All other languages are translations of the original instructions. ▪ The precautions described in this document cover very important topics, follow them carefully.
  • Page 6: For The Installer

    WARNING Improper installation or attachment of equipment or accessories could result in electrical shock, short-circuit, leaks, fire or other damage to the equipment. ONLY use accessories, optional equipment and spare parts made or approved by Daikin unless otherwise specified. WARNING Make sure installation, testing and applied materials comply with applicable legislation (on top of the instructions described in the Daikin documentation).
  • Page 7: Installation Site

    General safety precautions WARNING Provide adequate measures to prevent that the unit can be used as a shelter by small animals. Small animals that make contact with electrical parts can cause malfunctions, smoke or fire. CAUTION Wear adequate personal protective equipment (protective gloves, safety glasses,…) when installing, maintaining or servicing the system.
  • Page 8 WARNING Make sure installation, servicing, maintenance and repair comply with instructions from Daikin and with applicable legislation (for example national gas regulation) and are executed ONLY by authorised persons. WARNING If one or more rooms are connected to the unit using a duct system, make sure: ▪...
  • Page 9: Refrigerant - In Case Of R410A Or R32

    General safety precautions Installation space requirements WARNING If appliances contain R32 refrigerant, the floor area of the room in which the appliances are installed, operated and stored MUST be larger than the minimum floor area defined in table below A (m ).
  • Page 10 General safety precautions DANGER: RISK OF EXPLOSION Pump down – Refrigerant leakage. If you want to pump down the system, and there is a leak in the refrigerant circuit: ▪ Do NOT use the unit's automatic pump down function, with which you can collect all refrigerant from the system into the outdoor unit.
  • Page 11: Brine

    General safety precautions ▪ Whether the unit is factory charged with refrigerant or non-charged, in both cases you might need to charge additional refrigerant, depending on the pipe sizes and pipe lengths of the system. ▪ ONLY use tools exclusively for the refrigerant type used in the system, this to ensure pressure resistance and prevent foreign materials from entering into the system.
  • Page 12: Water

    General safety precautions 2.2.5 Water If applicable. See the installation manual or installer reference guide of your application for more information. NOTICE Make sure water quality complies with EU directive 2020/2184. 2.2.6 Electrical DANGER: RISK OF ELECTROCUTION ▪ Turn OFF all power supply before removing the switch box cover, connecting electrical wiring or touching electrical parts.
  • Page 13 General safety precautions CAUTION ▪ When connecting the power supply: connect the earth cable first, before making the current-carrying connections. ▪ When disconnecting the power supply: disconnect the current-carrying cables first, before separating the earth connection. ▪ The length of the conductors between the power supply stress relief and the terminal block itself MUST be as such that the current-carrying wires are tautened before the earth wire is in case the power supply is pulled loose from the stress relief.
  • Page 14: Specific Installer Safety Instructions

    Specific installer safety instructions 3 Specific installer safety instructions Always observe the following safety instructions and regulations. Unit installation (see "6 Unit installation" [  24]) WARNING Installation shall be done by an installer, the choice of materials and installation shall comply with the applicable legislation. In Europe, EN378 is the applicable standard. "6.1 Preparing the installation site" [  24])
  • Page 15 Specific installer safety instructions WARNING Connect the refrigerant piping securely before running the compressor. If the refrigerant piping is NOT connected and the stop valve is open when the compressor is run, air will be sucked in. This will cause abnormal pressure in the refrigeration cycle, which may result in equipment damage and even injury.
  • Page 16 Specific installer safety instructions WARNING ▪ All wiring MUST be performed by an authorised electrician and MUST comply with the national wiring regulation. ▪ Make electrical connections to the fixed wiring. ▪ All components procured on-site and all electrical construction MUST comply with the applicable legislation.
  • Page 17 Specific installer safety instructions DANGER: RISK OF ELECTROCUTION Disconnect the power supply for more than 10 minutes, and measure the voltage at the terminals of main circuit capacitors or electrical components before servicing. The voltage MUST be less than 50 V DC before you can touch electrical components. For the location of the terminals, see the wiring diagram.
  • Page 18 Specific installer safety instructions WARNING Prevent hazards due to inadvertent resetting of the thermal cut-out: power to this appliance MUST NOT be supplied through an external switching device, such as a timer, or connected to a circuit that is regularly turned ON and OFF by the utility. WARNING: MILDLY FLAMMABLE MATERIAL The refrigerant inside this unit is mildly flammable.
  • Page 19: About The Box

    About the box 4 About the box Keep the following in mind: ▪ At delivery, the unit MUST be checked for damage and completeness. Any damage or missing parts MUST be reported immediately to the claims agent of the carrier. ▪...
  • Page 20: To Unpack The Indoor Unit

    About the box 4.2.1 To unpack the indoor unit 4.2.2 To remove the accessories from the indoor unit 1 Remove: ▪ the accessory bag located at the bottom of the package, ▪ the mounting plate attached to the back of the indoor unit. 1×...
  • Page 21: About The Unit

    About the unit 5 About the unit WARNING: MILDLY FLAMMABLE MATERIAL The refrigerant inside this unit is mildly flammable. 5.1 System layout NOTICE Design of the system must not be done at temperatures below –15°C. a Indoor unit b Service lid c Air filter d Titanium apatite deodorizing and silver particle filter e Refrigerant piping, drain hose and interconnection cable...
  • Page 22: About The Wireless Lan

    About the unit 5.3 About the wireless LAN For detailed specifications, installation instructions, setting methods, FAQ, declaration of conformity and the latest version of this manual, visit app.daikineurope.com. 5.3.1 Precautions when using the wireless LAN Do NOT use near: ▪ Medical equipment.
  • Page 23 About the unit INFORMATION Scan the QR code to download and install the ONECTA app on your mobile phone or tablet: FTXP20~35N5V1B9 + ATXP20~35N5V1B9 Installer reference guide Split system air conditioners 4P751614-1 – 2023.08...
  • Page 24: Unit Installation

    Unit installation 6 Unit installation In this chapter Preparing the installation site ..............................6.1.1 Installation site requirements of the indoor unit ....................Opening the indoor unit ................................. 6.2.1 To remove the front panel............................. 6.2.2 To re-install the front panel ........................... 6.2.3 To remove the front grille............................
  • Page 25 Unit installation ▪ Wall strength. Check whether the wall or the floor is strong enough to support the weight of the unit. If there is a risk, reinforce the wall or the floor before installing the unit. Install power cables at least 1  metre away from televisions or radios to prevent interference.
  • Page 26: Opening The Indoor Unit

    Unit installation 6.2 Opening the indoor unit 6.2.1 To remove the front panel 1 Hold the front panel by the panel tabs on both sides and open it. a Panel tabs 2 Remove the front panel by sliding it to the left or the right and pulling it toward you.
  • Page 27: To Re-Install The Front Grille

    Unit installation b Symbol with 3 circles 4 We recommend opening the flap before removing the front grille. 5 Place both hands under the centre of the front grille, push it up and then toward you. 6.2.4 To re-install the front grille 1 Install the front grille and firmly engage the 3 upper hooks.
  • Page 28: Installing The Indoor Unit

    Unit installation a Service cover screw b Service cover 6.3 Installing the indoor unit 6.3.1 Precautions when installing the indoor unit INFORMATION Also read the precautions and requirements in the following chapters: ▪ General safety precautions ▪ Preparation 6.3.2 To install the mounting plate 1 Install the mounting plate temporarily.
  • Page 29: To Drill A Wall Hole

    Unit installation 6.3.3 To drill a wall hole CAUTION For walls containing a metal frame or a metal board, use a wall embedded pipe and wall cover in the feed-through hole to prevent possible heat, electrical shock, or fire. NOTICE Be sure to seal the gaps around the pipes with sealing material (field supply), in order to prevent water leakage.
  • Page 30: To Provide Drainage

    Unit installation NOTICE Do NOT use nippers to remove the pipe port cover, as this would damage the front grille. 6.3.5 To provide drainage Make sure condensation water can be evacuated properly. This involves: ▪ General guidelines ▪ Connecting the drain piping to the indoor unit ▪...
  • Page 31 Unit installation ▪ Condensation. Take measures against condensation. Insulate the complete drain piping in the building. 1 Insert the drain hose in the drain pipe as shown in the following figure, so it will NOT be pulled out of the drain pipe. To connect the piping on right side, right-back, or right-bottom INFORMATION The factory default is right-side piping.
  • Page 32 Unit installation 3 Insert the drain hose on the left side and do not forget to tighten it with the fixing screw; otherwise water leakage may occur. a Insulation fixing screw b Drain hose 4 Attach the drain hose to the refrigerant piping bottom side using adhesive vinyl tape.
  • Page 33: Piping Installation

    Piping installation 7 Piping installation In this chapter Preparing refrigerant piping ..............................7.1.1 Refrigerant piping requirements ........................... 7.1.2 Refrigerant piping insulation..........................Connecting the refrigerant piping............................7.2.1 About connecting the refrigerant piping....................... 7.2.2 Precautions when connecting the refrigerant piping.................... 7.2.3 Guidelines when connecting the refrigerant piping....................7.2.4 Pipe bending guidelines ............................
  • Page 34: Refrigerant Piping Insulation

    Piping installation 7.1.2 Refrigerant piping insulation ▪ Use polyethylene foam as insulation material: with a heat transfer rate between 0.041 and 0.052  W/mK (0.035 and 0.045 kcal/mh°C) with a heat resistance of at least 120°C ▪ Insulation thickness: Pipe outer diameter (Ø ) Insulation inner diameter Insulation thickness (t) (Ø...
  • Page 35: Guidelines When Connecting The Refrigerant Piping

    Piping installation NOTICE ▪ Do NOT use mineral oil on flared part. ▪ NEVER install a drier to this R32 unit to guarantee its lifetime. The drying material may dissolve and damage the system. NOTICE Take the following precautions on refrigerant piping into account: ▪...
  • Page 36: Pipe Bending Guidelines

    Piping installation a Torque wrench b Spanner c Piping union d Flare nut Piping size (mm) Tightening torque Flare dimensions Flare shape (mm) (N•m) (A) (mm) 90° ±2 Ø6.4 15~17 8.7~9.1 ØA Ø9.5 33~39 12.8~13.2 0.4~0.8 Ø12.7 50~60 16.2~16.6 7.2.4 Pipe bending guidelines Use a pipe bender for bending.
  • Page 37: To Connect The Refrigerant Piping To The Indoor Unit

    Piping installation a Flare’s inner surface MUST be flawless. b The pipe end MUST be evenly flared in a perfect circle. c Make sure the flare nut is fitted. 7.2.6 To connect the refrigerant piping to the indoor unit WARNING: MILDLY FLAMMABLE MATERIAL The refrigerant inside this unit is mildly flammable.
  • Page 38: Electrical Installation

    Electrical installation 8 Electrical installation 8.1 Preparing electrical wiring 8.1.1 About preparing electrical wiring INFORMATION Also read the precautions and requirements in the "2  General safety precautions" [  5]. WARNING ▪ If the power supply has a missing or wrong N-phase, equipment might break down.
  • Page 39: Precautions When Connecting The Electrical Wiring

    Electrical installation 8.2.2 Precautions when connecting the electrical wiring DANGER: RISK OF ELECTROCUTION WARNING ▪ All wiring MUST be performed by an authorised electrician and MUST comply with the national wiring regulation. ▪ Make electrical connections to the fixed wiring. ▪...
  • Page 40 Electrical installation To prepare stranded conductor wire for installation Method 1: Twisting conductor 1 Strip insulation (20 mm) from the wires. 2 Slightly twist the end of the conductor to create a "solid-like" connection. Method 2: Using round crimp-style terminal 1 Strip insulation from wires and slightly twist the end of each wire.
  • Page 41: Specifications Of Standard Wiring Components

    Electrical installation 8.2.4 Specifications of standard wiring components Component Power supply cable Voltage 220~240 V Phase Frequency 50 Hz Wire sizes Must comply with applicable legislation Interconnection cable Minimum cable section of 2.5 mm² and applicable for 220~240 V Recommended field fuse 20 A Earth leakage circuit breaker Must comply with applicable legislation 8.2.5 To connect the electrical wiring to the indoor unit...
  • Page 42: To Connect To An Ha System (Wired Remote Controller, Central Remote Controller, Wireles Adaptor, Etc.)

    Electrical installation 3 Pass the interconnection cable from the outdoor unit through the feed- through wall hole, through the back of the indoor unit and through the front side. Note: In case the interconnection cable was stripped in advance, cover the ends with insulating tape.
  • Page 43 Electrical installation a HA connector(S21 ) FTXP20~35N5V1B9 + ATXP20~35N5V1B9 Installer reference guide Split system air conditioners 4P751614-1 – 2023.08...
  • Page 44: Finishing The Indoor Unit Installation

    Finishing the indoor unit installation 9 Finishing the indoor unit installation 9.1 To insulate the drain piping, refrigerant piping and interconnection cable 1 After the drain piping, refrigerant piping and the electrical wiring are finished. Wrap refrigerant piping, interconnection cable and drain hose together using insulation tape.
  • Page 45: To Fix The Unit On The Mounting Plate

    Finishing the indoor unit installation 2 Pass the drain hose and refrigerant piping through the wall hole and seal the gap with a putty. 9.3 To fix the unit on the mounting plate 1 Set the indoor unit on the mounting plate hooks. Use the " " marks as a guide.
  • Page 46: Configuration

    Configuration 10 Configuration 10.1 To set a different channel of the indoor unit infrared signal receiver In case 2 indoor units are installed in 1 room, different addresses for 2 user interfaces can be set. 1 Remove the batteries from the user interface. 2 Cut the address jumper.
  • Page 47 Configuration ON/OFF a Operation lamp b Indoor unit ON/OFF switch 8 Press the indoor unit ON/OFF switch while the operation lamp is blinking. Jumper Address Factory setting After cutting with nippers INFORMATION If the setting could NOT be completed while the operation lamp was blinking, repeat the setting process from the beginning.
  • Page 48: Commissioning

    Commissioning 11 Commissioning 11.1 Overview: Commissioning This chapter describes what you have to do and know to commission the system after it is installed. Typical workflow Commissioning typically consists of the following stages: Checking the "Checklist before commissioning". Performing a test run for the system. 11.2 Checklist before commissioning 1 After the installation of the unit, check the items listed below.
  • Page 49: To Perform A Test Run

    Commissioning The correct pipe size is installed and the pipes are properly insulated. The stop valves (gas and liquid) on the outdoor unit are fully open. 11.3 To perform a test run Prerequisite: The power supply MUST be in the specified range. Prerequisite: Test run may be performed in cooling or heating mode.
  • Page 50: Hand-Over To The User

    Hand-over to the user 12 Hand-over to the user Once the test run is finished and the unit operates properly, make sure the following is clear for the user: ▪ Make sure that the user has the printed documentation and ask him/her to keep it for future reference.
  • Page 51: Disposal

    Disposal 13 Disposal NOTICE Do NOT try to dismantle the system yourself: dismantling of the system, treatment of the refrigerant, oil and other parts MUST comply with applicable legislation. Units MUST be treated at a specialised treatment facility for reuse, recycling and recovery. FTXP20~35N5V1B9 + ATXP20~35N5V1B9 Installer reference guide Split system air conditioners...
  • Page 52: Technical Data

    Technical data 14 Technical data ▪ A subset of the latest technical data is available on the regional Daikin website (publicly accessible). ▪ The full set of latest technical data is available on the Daikin Business Portal (authentication required). 14.1 Wiring diagram The wiring diagram is delivered with the unit, located inside of the outdoor unit (bottom side of the top plate).
  • Page 53 Technical data Symbol Meaning BZ, H*O Buzzer Capacitor AC*, CN*, E*, HA*, HE*, HL*, HN*, HR*, Connection, connector MR*_A, MR*_B, S*, U, V, W, X*A, K*R_*, NE D*, V*D Diode Diode bridge DIP switch Heater FU*, F*U, (for characteristics, refer to Fuse PCB inside your unit) Connector (frame ground)
  • Page 54 Technical data Symbol Meaning Q*DI, KLM Earth leak circuit breaker Overload protector Thermo switch Residual current device Resistor Thermistor Receiver Limit switch Float switch S*NG Refrigerant leak detector S*NPH Pressure sensor (high) S*NPL Pressure sensor (low) S*PH, HPS* Pressure switch (high) S*PL Pressure switch (low) Thermostat...
  • Page 55 Optional equipment Equipment made or approved by Daikin that can be combined with the product according to the instructions in the accompanying documentation. Field supply Equipment NOT made by Daikin that can be combined with the product according to the instructions in the accompanying documentation.
  • Page 56 DAIKIN ISITMA VE SOĞUTMA SİSTEMLERİ SAN.TİC. A.Ş. Gülsuyu Mahallesi, Fevzi Çakmak Caddesi, Burçak Sokak, No:20, 34848 Maltepe İSTANBUL / TÜRKİYE Tel: 0216 453 27 00 Faks: 0216 671 06 00 Çağrı Merkezi: 444 999 0 Web: www.daikin.com.tr 4P751614-1 2023.08 Verantwortung für Energie und Umwelt...