Daikin FTXP20-71L Service Manual page 130

Table of Contents

Advertisement

3
|
Components
To perform an electrical check of the specific thermistor
Service manual
130
Is the thermistor correctly installed
(thermal contact between the
thermistor and the piping)?
Yes
No
1 First perform a mechanical check of the thermistor, see
4
procedures" [
 129].
2 Locate the thermistor.
INFORMATION
Remove the thermistor from its holder if not reachable with a contact thermometer.
3 Measure the temperature using a contact thermometer.
Name
Symbol
Air
R1T
thermistor
Heat
R2T
exchanger
thermistor
Discharge
R3T
pipe
thermistor
Indoor unit
R1T
air (room)
thermistor
Heat
R2T
exchanger
thermistor
4 Determine the thermistor resistance that matches the measured
temperature.
Thermistor – Table A
T °C
T °C
–20
197.81
10
Action
Perform an electrical check of the
specific thermistor, see
procedures" [
Correctly install the thermistor, see
"Repair
procedures" [
Location
Connector
(PCB)
(pins)
Main (O/U) S90:1‑2
Main (O/U) S90:3‑4
Main (O/U) S90:5‑6
Display PCB
S26:1‑2
on main
PCB (I/U)
Main (I/U)
S32:1‑2
T °C
39.96
40
10.63
ATXP20~35 + FTXP20~71 + ARXP20~35 + RXP20~71
"Checking
4
 129].
4
 133].
"Checking
Inter-
Referen
mediate
ce
connector
(table)
(pins)
-
A
-
A
-
A
S27:1‑2 (on
B
display PCB)
-
A
T °C
70
3.44
Split Comfora R32
ESIE18-01E – 2023.01

Advertisement

Table of Contents