2.6.10 Unit discharges white mist
2.6.11 Swing flap does not operate
ATXP20~35 + FTXP20~71 + ARXP20~35 + RXP20~71
Split Comfora R32
ESIE18-01E – 2023.01
Check
Check installation conditions.
Check installation conditions.
Air filter.
Fan motor.
Symptom
Swing flap does not
operate
Detail
▪
Humid site.
▪
Dirty site.
▪
Oil mist.
Dirty heat exchanger.
Dirty air filter.
Defective fan motor.
Check
Check swing flap motor
Check indoor unit PCB
2
Troubleshooting
|
Detail
Some functions can force
the swing flap into a fixed
position, although swing
mode is selected on the
remote controller. This is
not a unit error, but a
control function to
prevent draft to the
customer.
Connector connection
Service manual
45