Commissioning
Setting lower pressure value
1
Desired pressure for lower pressure value ("empty pressure") is present at device.
2
3
4
5
The pressure present was saved as the lower pressure value
("empty pressure") and assigned to the lower level value
("empty calibration").
Setting upper pressure value
1
Desired pressure for upper pressure value ("full pressure") is present at device.
2
3
4
5
The pressure present was saved as the upper pressure value
("full pressure") and assigned to the upper level value ("full
8.3
Commissioning with an operating menu
Commissioning comprises the following steps:
• Function check
• Selection of the language, measuring mode and pressure unit → 28
• Position adjustment/zero adjustment → 30
• Configuring measurement:
• Pressure measurement → 31
• Level measurement → 31
8.3.1
Selecting the language, measuring mode and pressure unit
Language (000)
Navigation
Write permission
Description
28
Press the "Zero" key for at least 3 s.
Does the LED on the electronic insert light up briefly?
Yes
Press the "Span" key for at least 3 s.
Does the LED on the electronic insert light up briefly?
Yes
calibration").
Main menu → Language
Operators/Service engineers/Expert
Select the menu language for the local display.
Cerabar M PMC51, PMP51, PMP55
No
Applied pressure was not saved as the lower
pressure value. Observe the input limits.
No
Applied pressure was not saved as the upper
pressure value. Observe the input limits.
Endress+Hauser