Operation
Menu path: Setup → Extended setup → Current output → Set URV
Set URV
1
1 0 0 . 0 0 0
2
1 0 0 . 0 0 0
3
5 0 0 . 0 0 0
4
5 0 0 . 0 0 0
5
5 0 ¿ . 0 0 0
6
5 0 .
0 0 0
6.4.4
Operating example: Accepting the pressure present
Example: Setting pos. zero adjustment.
Menu path: Main menu → Setup → Pos. zero adjust
Pos. zero adjust
1 Cancel
Confirm
2
Cancel
Confirm
3
Adjustment has
been accepted!
4 Cancel
Confirm
24
014
Operation
The local display shows the parameter to be changed. The "mbar" unit is
mbar
defined in another parameter and cannot be changed here.
Press or to enter the edit mode.
mbar
The first digit is highlighted in black.
Use the key to change "1" to "5".
mbar
Press the key to confirm "5". The cursor jumps to the next position
(highlighted in black).
Confirm "0" with (second position).
The third digit is highlighted in black and can now be edited.
mbar
Use the key to change to the "
mbar
Use to save the new value and exit edit mode. See next graphic.
The new value for the upper range value is 50 mbar (0.75 psi).
mbar
Use to exit the edit mode for the parameter.
Use or to return to the edit mode.
007 Operation
The pressure for pos. zero adjustment is present at the device.
Use or to switch to the "Confirm" option. The active option is highlighted in
black.
Use the key to accept the applied pressure as zero adjustment. The device
confirms the adjustment and goes back to the "Pos. zero adjust" parameter.
Use to exit the edit mode for the parameter.
Cerabar M PMC51, PMP51, PMP55
" symbol.