Endress+Hauser Cerabar M PMC41 Technical Information

Endress+Hauser Cerabar M PMC41 Technical Information

Process pressure measurement pressure transmitter with ceramic and metal sensors overload-resistant and function-monitored with analog, hart or profibus pa electronics
Hide thumbs Also See for Cerabar M PMC41:
Table of Contents

Advertisement

Technical Information
Cerabar M PMC41/45, PMP41/45/46/48
Process pressure measurement
Pressure transmitter with ceramic and metal sensors
Overload-resistant and function-monitored
With Analog, HART or PROFIBUS PA Electronics
Application
The Cerabar M pressure transmitters measure
overpressure and absolute pressure in gases, steam,
liquids and dusts. Thanks to the modular instrument
concept, Cerabar M suits all areas of process engineering.
All hygienic connections, threaded connections and
flanges (also as diaphragm seals) are available as process
connections.
TI399P/00/en/06.08
71064497
Your benefits
• Performance characteristics
– Reference accuracy better than 0.2% of the set
measuring range
(optional: non-linearity better than 0.1%)
– Configurable measuring range up to TD 10:1
– Long-term stability better than 0.25 % / 3 years
• Deployed for pressure monitoring up to SIL 2 as per
IEC 61508/IEC 61511-1
• Sensors
– Dry capacitance ceramic sensor (Ceraphire
measuring ranges up to 40 bar - overload-resistant,
vacuum-proof, stable against alternating load
– Piezoresistive sensor with metal diaphragm for
measuring ranges up to 400 bar
• Output signals: 4 to 20 mA, 4 to 20 mA with HART,
PROFIBUS PA
• Housing
With its stainless steel housing with no dead space,
Cerabar M meets the hygienic requirements of the
food and pharmaceutical industries.
The coated aluminum housing has already stood the
test of time in the process industry.
• Device versions compliant with ASME-BPE
®
) for

Advertisement

Table of Contents
loading

Summary of Contents for Endress+Hauser Cerabar M PMC41

  • Page 1 Technical Information Cerabar M PMC41/45, PMP41/45/46/48 Process pressure measurement Pressure transmitter with ceramic and metal sensors Overload-resistant and function-monitored With Analog, HART or PROFIBUS PA Electronics Application Your benefits The Cerabar M pressure transmitters measure • Performance characteristics overpressure and absolute pressure in gases, steam, –...
  • Page 2: Table Of Contents

    Ex approvals ........66 Reference accuracy ........23 Endress+Hauser...
  • Page 3 Safety conventions and icons ......82 Installation/Control Drawings ......82 Endress+Hauser...
  • Page 4: Function And System Design

    – Dry ceramic cell (without fill fluid), resistant to abrasion and corrosion, compliant with FDA: Ceraphire – Special cleaning of the transmitter to remove paint-wetting impairment substances, for use in paint shops Depends on the element of the selected components which has the lowest pressure rating Endress+Hauser...
  • Page 5: Overview Of Diaphragm Seals For Pmp46

    – DN 51 (2") clamp used ASME-BPE for use (MDM) in biotechnical P01-PMP46xxx-03-xx-xx-xx-005 processes; wetted surfaces Varivent – Type N for pipes PN 40 ≤ 0.4 *m DN 40 – DN 162 (15.75 *in; 180 grit), P01-PMP46xxx-03-xx-xx-xx-004 electropolished Endress+Hauser...
  • Page 6: Overview Of Diaphragm Seals For Pmp48

    – 80 A Flange with EN/DIN EN 1092-1/ – DN 50 Up to PN 40 extended flange DIN 2527 – DN 80 diaphragm seal ANSI ANSI B.16.5 – 2" Up to 150 lbs flange – 3" P01-PMP48xxx-03-xx-xx-xx-005 – 4" Endress+Hauser...
  • Page 7: Measuring Principle

    The pressure-dependent change in the bridge output voltage is measured and processed further. Advantages: • Can be used with process pressures up to 400 bar • High long-term stability • Guaranteed overload resistance up to 4 times the nominal pressure (max. 600 bar) Endress+Hauser...
  • Page 8: Communication Protocol

    • 4 to 20 mA with HART communication protocol • PROFIBUS PA – The Endress+Hauser devices meet the FISCO model requirements. – Due to the low current consumption of 11 mA ±1 mA the following can be operated at one bus segment when installing to FISCO: –...
  • Page 9: Human Interface

    Bar graph, display of current measured value ➂ Lower-range value ➃ Upper-range value ➄ Set measuring range in measuring limits ➅ Display of calibration point (Z (Zero) = lower-range value (LRV) or S (Span) = upper-range value (URV)) ➆ Nominal measuring range Endress+Hauser...
  • Page 10: Operating Elements

    • Setting the lower-range value and upper-range value – reference pressure applied at the device • Setting the bus address of the device Handheld terminals – HART With a handheld terminal, all the parameters can be configured anywhere along the 4 to 20 mA line via menu operation. Endress+Hauser...
  • Page 11: Fieldcare - Hart, Profibus Pa

    FieldCare is Endress+Hauser's plant asset management tool which is based on FDT technology. With PROFIBUS PA FieldCare, you can configure all of Endress+Hauser devices, as well as devices from other manufacturers that support the FDT standard. FieldCare supports the following functions: •...
  • Page 12: Input

    Table above). Please also observe the pressure-temperature dependencies. For the appropriate standards and further information, see Page 30, "Pressure specifications" section. Version in the order code → see also Page 67 ff, feature 30 "Sensor range; MWP, OPL" Endress+Hauser...
  • Page 13 Observe the pressure and temperature operating limits of the filling oil selected. → See Page 60, "Diaphragm seal filling oils" section. Version in the order code → see also Page 67 ff, feature 30 "Sensor range; MWP, OPL" Absolute pressure sensors Not for PMP46 Endress+Hauser...
  • Page 14: Explanation Of Terms

    Set span ➁ This span is based on the zero point. Span based on zero point ➂ Nominal value i upper-range limit (URL) ➃ Nominal measuring range ➄ Sensor measuring range Lower-range limit Upper-range limit Lower-range value Upper-range value Endress+Hauser...
  • Page 15: Output

    – Current output: – Typical value: 1 μA – Max.: 6 μA – Onsite display: 28 segments, numerical value display with 1 per thousand resolution • PROFIBUS PA: – Onsite display: 28 segments, display value with resolution 1 per thousand Endress+Hauser...
  • Page 16: Dead Time, Time Constant (T63)

    Dead time t Time constant (T63), t 540 ms 240 ms PMP46/PMP48 additional influence from the diaphragm seal Reading cycle HART commands: on average 3 to 4 per second on average. Update rate On average 250 to 330 ms. Endress+Hauser...
  • Page 17: Dynamic Behavior Profibus Pa

    • Via handheld terminal or PC with operating program, continuous 0 to 40 s • Factory setting: 2 s PROFIBUS PA • Via handheld terminal or PC with operating program, continuous 0 to 40 s • Factory setting: 0.0 s Endress+Hauser...
  • Page 18: Power Supply

    4 to 20 mA test signal via the terminal lugs 50 mA fuse (slow-blow). without interrupting the measurement. ➁ 4 to 20 mA test signal: you can take a 4 to 20 mA test signal via the terminal lugs without interrupting the measurement. Endress+Hauser...
  • Page 19 P01-PMx4xxxx-04-xx-xx-xx-004 Left: electrical connection for devices with M12 connector Right: view of the connector at the device Endress+Hauser offers the following accessories for devices with M12 connectors: Plug-in jack M 12x1, straight • Material: body PA; coupling nut CuZn, nickel-plated •...
  • Page 20: Supply Voltage

    → See also Page 67 ff, feature 20 "Housing; Electrical connection". Cable entry Cable specification • Endress+Hauser recommends using shielded, twisted pair two-wire cables. • Terminals for wire cross-sections 0.14 to 2.5 mm • Cable outer diameter: 5 to 9 mm...
  • Page 21: Performance Characteristics - General

    (LRL) = –1 bar 5 % URL • Example 2: ➁ • Sensor measuring range: –1 to 10 bar • Extended measuring rang: –1 to 10.5 bar (the zero point P01-xxxxxxxx-05-xx-xx-xx-024 can be adjusted in this range) Case 2 Endress+Hauser...
  • Page 22: Vibrations Effects

    • 4 to 20 mA: 60 ms • 4 to 20 mA HART: 220 ms • PROFIBUS PA: 220 ms Settling time • 4 to 20 mA: 180 ms • 4 to 20 mA HART: 600 ms • PROFIBUS PA: 600 ms Endress+Hauser...
  • Page 23: Performance Characteristics - Ceramic Diaphragm

    4...20 mA HART, PROFIBUS PA –10...+60 °C –40...–10 °C, +60...+85 °C +85...+125 °C (+185 to +257°F) % of URL/10 K (+14 to +140°F) (-40 to +14°F, +140 to +185°F) (only PMC45) ⎯ ⎯ • ±0.08 ⎯ ⎯ • ±0.1 ⎯ ⎯ • ±0.12 Endress+Hauser...
  • Page 24: Performance Characteristics - Metal Diaphragm

    4...20 mA –10...+60 °C –40...–10 °C, +60...+85 °C +85...+125 °C (+185 to +257°F) % of URL/10 K (+14 to +140°F) (-40 to +14°F, +140 to +185°F) (only PMP45) ⎯ ⎯ • ±0.15 ⎯ ⎯ • ±0.2 ⎯ ⎯ • ±0.25 Endress+Hauser...
  • Page 25: Operating Conditions (Installation)

    Diaphragm seals also shift the zero point, depending on the installation position (→ see also Page 65, "Installation instructions, diaphragm seal systems" section). • Endress+Hauser offers a mounting bracket for installing on pipes. → See also Page 26, "Wall and pipe- mounting" section.
  • Page 26: Wall And Pipe-Mounting

    Cerabar M Wall and pipe-mounting Endress+Hauser offers a mounting bracket for installing on pipes or walls for PMC41, PMP41, PMP46 and PMP48. You can order the mounting bracket either via the order code (→ see Page 68 ff, feature 60, "Additional option") or separately as an accessory.
  • Page 27: Oxygen Applications

    → see Page 67 ff "Ordering information", feature 80 "Sensor seal". Ultrapure gas applications Endress+Hauser also provides devices which have been cleaned of oil and grease for special applications, such as ultrapure gas. No special restrictions regarding the process conditions apply to these devices.
  • Page 28: Operating Conditions (Environment)

    For high-temperature applications, either a PMP46/48 with a temperature isolator or with a capillary can be used. If vibrations also occur in the application, Endress+Hauser recommends you use a PMP46/48 with a capillary.If a PMP46/48 with a temperature isolator or capillary is used, we recommend a suitable bracket for mounting (see "Wall and pipe-mounting"...
  • Page 29: Operating Conditions (Process)

    –40 to +100°C (–40 to +212°F) PMC45 (with ceramic measuring diaphragm) Version for feature 80 Seal Temperature operating range in the order code FKM Viton –20 to +125°C/150°C (–4 to +257°F/302°F) EPDM (FDA 21CFR177.2600); 3A Class II; USP Class –20 to +125 °C/150 °C Endress+Hauser...
  • Page 30: Pressure Specifications

    With regard to their stability-temperature property, the materials 1.4435 and 1.4404 are grouped together under 13EO in EN 1092-1 Tab. 18. The chemical composition of the two materials can be identical. The equation does not apply for PMP41, PMP45 and PMP48 with a 100 bar measuring cell. Endress+Hauser...
  • Page 31: Mechanical Construction

    Thread ISO 228 G 1/2 A, version 1M: AISI 316L, version 2M: Alloy C276 (2.4819) ➁ Thread ISO 228 G 1/2 A bore 11.4 mm, version 1R: AISI 316L ➂ Thread ISO 228 G 1/2 A G 1/4 (female), version 1P: AISI 316L Endress+Hauser...
  • Page 32 Version 1K: thread JIS B0203 R 1/2 (male) bore 11.4 mm, material: AISI 316L M 20 x 1.5 ø8 ø3 ø6 M 20 x 1.5 P01-PMC41xxx-06-09-xx-xx-003 Process connection PMC41, version 1T: thread DIN 13 M20 x 1.5 bore 3 mm, material AISI 316L Endress+Hauser...
  • Page 33: Process Connections Pmc45

    Process connections PMC45, threaded connection, material AISI 316L ➀ Version AG: thread ISO 228 G1 1/2 A Endress+Hauser also offers welding necks for this process connection. See the following section. ➁ Version AR: thread ISO 228 G 2 A ➂...
  • Page 34 Welding neck for process connection thread ISO 228 G 1 1/2 A (version AG) order no.: 52024469, order no. with 3.1 inspection certificate: 52024470 Note! Endress+Hauser offers a pressure sensor dummy for the welding necks with order numbers 52024469 and 52024470. Order number for pressure sensor dummy: 52024471 Tri-Clamp, flush-mounted diaphragm ø26...
  • Page 35 Version LB: Varivent type F for pipes DN 25 – DN 32 PN 40, EHEDG, 3A with HNBR or EPDM seal ➄ Version LL: Varivent type N for pipes DN 40 – DN 162 PN 40, EHEDG, 3A with HNBR or EPDM seal Endress+Hauser...
  • Page 36 Cerabar M ➅ Version KL: DRD DN50 (65 mm) PN25, 3A with HNBR or EPDM seal; Endress+Hauser offers a welding flange with PTFE seals for flush-mounted installation of a device with a DRD flange. See the following graphic. ➆ Version AH: DIN 11851 DN 40 PN 40, 3A with HNBR or EPDM seal ➇...
  • Page 37 AISI 316L – – AISI 316L DN 80 PN 10-40 B1 (D) AISI 316L – – Designations as per DIN 2527 in brackets ECTFE coating on AISI 316L. Avoid electrostatic charge at the plastic surfaces when using in hazardous areas. Endress+Hauser...
  • Page 38 Combination of AISI 316 for required pressure resistance and AISI 316L/1.4435 for required chemical resistance (dual rated) ECTFE coating on AISI 316L/1.4435. Avoid electrostatic charge at the plastic surfaces when using in hazardous areas. Max.: 15 bar (225 psi), max.: –10 to +60 °C (+14 to +140 °F) Endress+Hauser...
  • Page 39 Process connection PMC45, JIS flange with raised face RF (flush-mounted diaphragm), material: AISI 316L/1.4435 Flange Boltholes Version Nominal Nominal Diameter Thickness Raised face Quantity Diameter Hole circle Total weight diameter pressure [mm] [mm] [mm] [mm] [mm] [kg] 50 A 10 K 80 A 10 K Endress+Hauser...
  • Page 40 AISI 316L with inspection certificate EN 10204 3.1 material 52010174 85 mm AISI 316L 52006262 85 mm AISI 316L with inspection certificate EN 10204 3.1 material 52010173 Welding nozzle 4 x 90° (=360°) ø42 ø52 ø64.9 ø74.9 P01-PMC45xxx-06-09-xx-xx-002 Version XU: welding nozzle 75 mm, material AISI 316L Endress+Hauser...
  • Page 41: Process Connections Pmp41 (With Metal Measuring Diaphragm)

    Can be selected in conjunction with versions A, C, D for feature 80 "Seal; Fill fluid" in the order code feature 80 "Seal; Fill fluid" in the order code (→ see Page 70) (→ see Page 70) SW 27 SW 25 SW 32 P01-PMP41xxx-06-09-xx-xx-004 P01-PMP41xxx-06-09-xx-xx-005 Endress+Hauser...
  • Page 42 This process connection can be selected with versions F or H for feature 80 "Seal; Fill fluid" (→ see Page 70). Note! Endress+Hauser offers a pressure sensor dummy for the welding necks with order numbers 52002643 and 52010172. Order number for pressure sensor dummy: 52005082 For screw-in hole G ½...
  • Page 43: Process Connections Pmp45 (With Metal Measuring Diaphragm)

    100 bar ➂ Version BB: thread ANSI 3/4 MNPT Note! Endress+Hauser offers a pressure sensor dummy for the welding necks with order numbers 52005087 and 52010171. Order number for pressure sensor dummy: 52005272 Clamp connections ➀ ➁...
  • Page 44 Version LB: Varivent type F for pipes DN 25 – DN 32 PN 40, EHEDG, 3A ➃ Version LG: Varivent type B for pipes DN 10 – DN 15 PN 40, EHEDG, 3A ➄ Version AB: DIN 11851 DN 25 PN 40, 3A Endress+Hauser...
  • Page 45: Process Connections Pmp46 (With Metal Measuring Diaphragm)

    – +0.3 +0.18 ≤ 0.4 μm (15.75 min; 240 grit), electropolished; Diaphragm seal versions compliant with ASME-BPE for use in biochemical processes, wetted surfaces R to be ordered using feature 60 "Additional option", version "P" in the order code Endress+Hauser...
  • Page 46 DN 25 22.5 43.5 50.5 +7.75 +4.49 DN 16 15.7 +5.4 +16.9 DN 38 1 1/2 35.5 43.5 50.5 +5.17 +3.46 DN 51 48.6 56.5 +3.56 +2.69 Including 3.1 and pressure test as per Pressure Equipment Directive, Category II Endress+Hauser...
  • Page 47 Process stallation total meter pres- diameter height weight sure [inch] [bar] [mm] [mm] [mm] [mm] [mm] [mbar/10 K] [mm] [kg] 1 1/2 PN 40 2 5/16 – 1/8" 21 +8.18 +2.59 PN 40 2 7/8 – 1/8" +5.4 +1.76 Endress+Hauser...
  • Page 48 Process connection PMP46, version KL: material AISI 316L, 3A, surface roughness of the surfaces in contact with the 0.8 μ m as standard. Lower surface roughness on request. medium R a ≤ Version Nominal pressure Ambient Process Max. total weight [mbar/10 K] [kg] PN 25 +2.26 +0.89 Endress+Hauser...
  • Page 49 [mm] [mm] [mm] [mm] [mbar/10 K] [mm] [kg] DN 32 PN 40 Rd 58 x 1/6 +8.14 +2.59 DN 40 PN 40 Rd 65 x 1/6 +5.4 +1.76 DN 50 PN 25 68.5 Rd 78 x 1/6 +2.21 +0.88 Endress+Hauser...
  • Page 50 [mm] [mm] [mm] [mbar/10 K] [mm] [kg] DN 25 PN 40 26.2 Rd 52 x 1/6 +16.03 +5.17 DN 40 PN 40 Rd 65 x 1/6 +5.4 +1.76 DN 50 PN 25 50.7 Rd 78 x 1/6 +2.21 +0.88 Endress+Hauser...
  • Page 51: Process Connections Pmp48 (With Metal Measuring Diaphragm)

    +5.17 G 1 1/2 A +5.4 +1.76 +1.76 +0.56 1 MNPT – +15.66 +4.21 1 1/2 MNPT 400 – +8.14 +2.59 2 MNPT – +5.4 +2.59 Endress+Hauser also offers welding necks for this process connection. → See Page 34. Endress+Hauser...
  • Page 52 PTFE seal as standard max. 260 °C/500 °F (higher temperatures on request) Version Measuring range Description Nominal pressure T Process Diaphragm seal weight [mbar/10 K] [kg] ≤ 40 bar ISO 228 G 1/2 B PN 40 +0.75 1.43 ≤ 40 bar ANSI 1/2 MNPT PN 40 +0.55 1.43 Endress+Hauser...
  • Page 53 PN 400 +3.45 +1.28 4.75 > 40 bar ANSI 1/2 MNPT PN 400 +3.45 +1.28 4.75 Note! With the use of high temperature oils the design can deviate strongly. For further information please contact your local Endress+Hauser Sales Center. Endress+Hauser...
  • Page 54 +1.67 DN 80 PN 10-40 B1 (D) +0.19 +0.7 Designation as per DIN 2527 in brackets Alternatively with 50 mm, 100 mom and 200 mm extended diaphragm seal, for extended diaphragm seal diameter and weight, see the following table Endress+Hauser...
  • Page 55 Process total meter pres- meter height diameter weight sure [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mbar/10 K] [kg] 25 A 10 K +16.03 +5.17 50 A 10 K +2.21 +1.15 80 A 10 K +0.19 +0.11 Endress+Hauser...
  • Page 56 1.12 0.75 3.50 +0.19 +0.11 316L 209.5 28.4 19.1 152.4 AISI 316/ 0.94 6.19 0.75 3.50 +0.19 +0.11 316L 228.6 23.9 157.2 19.1 190.5 AISI 316/ 1.25 6.19 0.88 7.88 3.50 +0.19 +0.11 12.9 316L 31.8 157.2 22.4 200.2 Endress+Hauser...
  • Page 57 [in] [lb./sq.in] [in] [(mm)] [in] [(mm)] [kg] 2 (50.8) 1.9 (48.3) 4 (101.6) 6 (152.4) 2 (50.8) 2.99 (75.9) 4 (101.6) 6 (152.4) 2 (50.8) 3.7 (94) 4 (101.6) 11.1 6 (152.4) 12.4 Endress+Hauser...
  • Page 58: Weight

    13EO in EN 1092-1 Tab. 18. The chemical composition of the two materials can be identical. Seals • For universal process adapter 44mm: silicone molded seal FDA 21CFR177.2600/USP Class VI-70C. • For all other seals, see Page 29, "Temperature operating range, seals" section. Endress+Hauser...
  • Page 59: Planning Instructions For Diaphragm Seal Systems

    The correlations between the individual diaphragm seal components are presented in the following section. For further information and comprehensive diaphragm seal system designs, please contact your local Endress+Hauser Sales Center. Diaphragm seal The diaphragm seal determines the application range of the system by •...
  • Page 60: Diaphragm Seal Filling Oils

    The volume change is the volume that has to be shifted to pass through the complete measuring range. Pressure transmitters from Endress+Hauser are optimized with regard to minimum volume change. Diaphragm seal filling oils...
  • Page 61: Influence Of The Temperature On The Zero Point

    Ambient from the diagram. Result: 8.4 mbar/10 K = 45 °C – 25 °C = 20 °C ⇒ 8.4 mbar/10 K x 20 K = 16.8 mbar – T Ambient Calibration Result: In this example, the zero point is shifted 16.8 mbar. Endress+Hauser...
  • Page 62 Diaphragm seal ➅ Tri-Clamp, ISO 2852 DN 51 (2"), DIN 32676 DN 50, AISI 316L ➆ Pipe diaphragm seal Tri-Clamp, ISO 2852 DN 25 (1"), AISI 316L Varivent type F for pipes DN 25 – DN 32 PN40, AISI 316L Endress+Hauser...
  • Page 63 Versions with 1 m (3 ft) capillary, see also feature 80 "Transmitter mounting; fill fluid" Diagrams for diaphragm seal PMP48 T Ambient [mbar/10 K] Capillary length P01-PMP48xxx-05-xx-xx-xx-000 Diagram T Ambient as a function of the capillary length for PMP48 Endress+Hauser...
  • Page 64 ANSI flange 1" 300 lbs RF, AISI 316/316L ANSI flange 1" 400/600 lbs RF, AISI 316/316L ANSI flange 1" 900/1500 lbs RF, AISI 316/316L ANSI flange 1" 2500 lbs RF, AISI 316/316L JIS flange 10K 25A RF, AISI 316L Endress+Hauser...
  • Page 65: Ambient Temperature Range

    • With a bending radius of ≥ 100 mm. Vacuum applications For applications under vacuum, Endress+Hauser recommends mounting the pressure transmitter below the diaphragm seal. This prevents a vacuum load of the diaphragm seal caused by the presence of fill fluid in the capillary.
  • Page 66: Certificates And Approvals

    CE mark The device meets the legal requirements of the relevant EC directive. Endress+Hauser confirms that the device has been tested successfully by attaching the CE mark. Ex approvals All explosion protection data are given in separate documentation which is available upon request. The Ex documentation is supplied as standard with all devices approved for use in hazardous areas.
  • Page 67: Ordering Information

    40 bar/4 MPa/600 psi 60 bar/6 MPa/900 psi Special version, to be specified Calibration; Unit: 0.2% sensor range; mbar/bar 0.2% sensor range; kPa/MPa 0.2 % sensor range; mmmH O/mH 0.2% sensor range; inH O/ftH 0.2% sensor range; kgf/cm 0.2% sensor range; psi Endress+Hauser...
  • Page 68 EPDM Chemraz Kalrez M Kalrez, cleaned for silicone-free service FKM Viton, cleaned from oil + grease FKM Viton, cleaned for silicone-free service FKM Viton, oxygen service note application limits pressure/temp Special version, to be specified PMC41 Complete order code Endress+Hauser...
  • Page 69: Pmc45

    0.2% sensor range; psi 0.2% see additional specification 0.1% see additional specification DKD certificate; see additional specification Special version, to be specified Output; Operation: 4 to 20 mA analog; without display 4 to 20 mA analog; display bar graph Endress+Hauser...
  • Page 70 10K 50 RF, 316L, flange JIS B2220 10K 80 RF, 316L, flange JIS B2220 Other Universal adapter 44 mm, EHEDG, 316L incl. silicone molded seal (CRN) Welding nozzle 75 mm, 316L Special version, to be specified Sensor seal: FKM Viton Endress+Hauser...
  • Page 71 Cerabar M Sensor seal: HNBR (FDA) EPDM (FDA) Chemraz Kalrez M Kalrez, cleaned for silicone-free service FKM Viton, cleaned from oil + grease FKM Viton, cleaned for silicone-free service Special version, to be specified PMC45 Complete order code Endress+Hauser...
  • Page 72: Pmp41

    Special version, to be specified Calibration; Unit: 0.2% sensor range; mbar/bar 0.2% sensor range; kPa/MPa 0.2 % sensor range; mmH O/mH 0.2% sensor range; inH O/ftH 0.2% sensor range; kgf/cm 0.2% sensor range; psi 0.2% see additional specification 0.1% see additional specification Endress+Hauser...
  • Page 73 FKM Viton, inert oil, cleaned from oil + grease NBR O-ring; synthetic oil FKM Viton O-ring; synthetic oil FTFE; synthetic oil Welded; mineral oil Welded; inert oil, oxygen service Welded, inert oil, cleaned from oil+grease Special version, to be specified PMP41 Complete order code Endress+Hauser...
  • Page 74: Pmp45

    Special version, to be specified Calibration; Unit: 0.2% sensor range; mbar/bar 0.2% sensor range; kPa/MPa 0.2 % sensor range; mmH O/mH 0.2% sensor range; inH O/ftH 0.2% sensor range; kgf/cm 0.2% sensor range; psi 0.2% see additional specification 0.1% see additional specification Endress+Hauser...
  • Page 75 KingGage 1777-2 (short), 316L, 3A KingGage 1777-2 (middle), 316L, 3A KingGage 1777-2 (long), 316L, 3A Special version, to be specified Diaphragm, Fill fluid: 316L, synthetic oil 316L, synthetic oil (FDA) Special version, to be specified PMP45 Complete order code Endress+Hauser...
  • Page 76: Pmp46

    0.2% sensor range; kgf/cm 0.2% sensor range; psi 0.2% see additional specification DKD certificate; see additional specification Special version, to be specified Output; Operation: 4 to 20 mA analog; without display 4 to 20 mA analog; display bar graph Endress+Hauser...
  • Page 77 M ..m capillary; low-temperature oil (capillary > 1 m, only as of DN 50/2"; capillary length: 1 – 10 m, price independent of length) ..m capillary; vegetable oil (FDA) (capillary > 1 m, only as of DN 50/2"; capillary length: 1 – 10 m, price independent of length) Endress+Hauser...
  • Page 78 3 – 33 ft, price independent of length) ..ft capillary; inert oil (capillary > 3 ft, only as of DN 50/2"; capillary length: 3 – 33 ft, price independent of length) Special version, to be specified PMP46 Complete order code Endress+Hauser...
  • Page 79: Pmp48

    0.2% sensor range; mbar/bar 0.2% sensor range; kPa/MPa 0.2 % sensor range; mmH O/mH 0.2% sensor range; inH O/ftH 0.2% sensor range; kgf/cm 0.2% sensor range; psi 0.2% see additional specification DKD certificate; see additional specification Special version, to be specified Endress+Hauser...
  • Page 80 2" 150 Ibs RF, 316/316L, 6" barrel, flange ANSI B16.5 (CRN) 3" 150 Ibs RF, 316/316L, 2" barrel, flange ANSI B16.5 (CRN) 3" 150 Ibs RF, 316/316L, 4" barrel, flange ANSI B16.5 (CRN) 3" 150 Ibs RF, 316/316L, 6" barrel, flange ANSI B16.5 (CRN) Endress+Hauser...
  • Page 81 Diaphragm material: Extended diaphragm seal versions only as 316L 316L Alloy C276 Tantalum 316L with 0.09 PTFE foil (not for vacuum applications) 316L with 0.25 PTFE foil (not for vacuum applications) Special version, to be specified PMP48 Complete order code Endress+Hauser...
  • Page 82: Additional Documentation

    – ZD052P CSA IS Class I, II, III, PMC41, PMC45, PMP41, – 4 to 20 mA – ZD040P Division 1, Groups A – G PMP45, PMP46, PMP48 – 4 to 20 mA HART – ZD040P – PROFIBUS PA – ZD051P Endress+Hauser...
  • Page 83 Cerabar M Endress+Hauser...
  • Page 84 Cerabar M Instruments International Endress+Hauser Instruments International AG Kaegenstrasse 2 4153 Reinach Switzerland Tel. +41 61 715 81 00 Fax +41 61 715 25 00 www.endress.com info@ii.endress.com TI399P/00/en/06.08 71064497 CCS/FM+SGML 6.0 71064497...

Table of Contents