YASKAWA CIMR-AC4A0103TAA Quick Start Manual page 14

Ac drive a1000

Advertisement

3 Electrical Installation
Wiring Specification
Main Circuit
Mains Connection
Use the fuses listed in the table below when wiring the main circuit and connect L1, L2, L3 as specified in drawing
Electrical Installation on page
Model
Mains Fuse
CIMR-A
[Bussmann]
4A0044
4A0058
4A0072
FWH-250A
4A0088
4A0103
4A0139
FWH-350A
4A0165
FWH-400
4A0044-0095
4A0058-0095
4A0072-0095
FWH-250A
4A0088-0095
4A0103-0095
4A0139-0095
FWH-350
4A0165-0095
FWH-400
<1> Use ferrules for flexible wire power supply cable
<2> Use ring cable terminals for earth cable connection at the EMC filter. Connect earth power supply earth directly to EMC filter earth terminal.
Motor Connection
Model
Applicable cable
CIMR-A
(mm
(all types)
4A0044
2.5 to 25
4A0058
4A0072
2.5 to 50
4A0088
16 to 50
4A0103
4A0139
25 to 95
4A0165
<1> Use ring cable terminals.
Control Circuit
The control terminal board is equipped with screwless terminals. Always use wires within the specification listed below.
Wire Type
Solid
Flexible
Flexible with ferrule (recommended)
EN 14
13.
Applicable
Recommended
cable (mm
)
cable (mm
2
16 to 25
16 to 50
25 to 50
35 to 95
50 to 95
16 to 25
16 to 50
50 to 95
Recommended
U/T1,V/T2,W/T3,
2
)
cable (mm
2
)
16
25
35
50
M10 18 to 23 Nm
70
L1 / L2 / L3
<1>
Ferrule Length
)
(mm, max.)
2
16
15
25
35
25
50
70
16
10
50
15
70
Drive Terminals
<1>
+3
– , +1, +2
M6
4 to 6 Nm
M8
9 to 11 Nm
M10 18 to 23 Nm
Wire size (mm
2
0.2 to 1.5
0.2 to 1.0
0.25 to 0.5
YASKAWA Europe TOEP C710606 96A - AC Drive A1000 IP54 Wallmount - Quick Start Guide
Screw Size / Tightening Torque (Nm)
M5 slotted
2 to 4 Nm
M6 slotted
2.5 to 5 Nm
M6
3 to 6 Nm
M8
6 to 12 Nm
M6
4 Nm
M10
22.6 Nm
Screw Size / Tightening Torque (Nm)
B1, B2
M5
2 to 2.5 Nm
M8
9 to 11 Nm
)
Ferrule Length (mm)
<2>
M8
9 to 11 Nm
M10
18 to 23 Nm
M8
9 to 11 Nm
M10
18 to 23 Nm
<1>
M8
9 to 11 Nm
M10
18 to 23 Nm
-
-
8