AUMA AC 01.2-22X Manual page 36

Multi-turn actuators with actuator controls
Table of Contents

Advertisement

Tests and maintenance
Test procedure
Test sequence
36
Configuration of "SIL seating"
= "no seating"
(Safe opening or closing without responding to any protective equipment)
For Safe ESD operation, the actuator has to perform the failure operation without
interruption. Limit switching and/or torque switching must not stop the failure operation
If "SIL seating = no seating" (without end position protection) is configured,
faulty operation during the test may result in damage to the elements within
the safety-related system.
Possible consequences: Valve damage, motor overheating, contactor seizure,
damage to the electronics, heating up or damage to cables.
Interrupt safety operation before reaching the end position (Set
ESDa
and
Safe ESDb
For the test, the valve should either be in mid-position or at sufficient distance
from the end positions.
In case of damage, the actuator system has to be checked and repaired, if ne-
cessary.
Information: For version with electronic control unit with limit switches, steps
6
9 are obsolete.
1.
Operate actuator in mid-position or at sufficient distance from end positions.
2.
Open the switch compartment
3.
Initiate safety operation:
Set
Safe ESDa
Limit switching evaluation
4.
Operate limit switches:
For "Safe CLOSING" (Safe ESD in direction CLOSE) configuration:
Turn test button [1] in direction of the LSC arrow.
For "Safe OPENING" (Safe ESD in direction OPEN) configuration: Turn
test button [2] in direction of the LSO arrow.
The safety function reaction to the limit switch signals is correct if safety opera-
tion is not stopped.
5.
After limit evaluation:
5.1 Set
Safe ESDa
fore reaching the end position.
5.2 Operate actuator via local controls or from REMOTE to end position OPEN
and then to end position CLOSED. (Positions will be recorded anew).
5.3 Operate actuator to mid-position or at sufficient distance from the end
positions.
Torque switching evaluation
6.
Initiate safety operation:
Set
Safe ESDa
SA .1 with AC 01.2-22X/-22Y/ACExC 01.2-22X/-22Y
input signals to +24 V DC).
and
Safe ESDb
input signal to 0 V (low).
and
Safe ESDb
input signals to +24 V DC (high) be-
and
input signal to 0 V (low).
Safe ESDb
Multi-turn actuators
Safe

Advertisement

Table of Contents
loading