AUMA AC 01.2-22X Manual page 18

Multi-turn actuators with actuator controls
Table of Contents

Advertisement

Installation, commissioning and operation
Information
Designation
Signal
Wiring diagram
Safe ESDa
Digital input for Safe ESD function
Safe ESDb
Redundant input for Safe ESD function
0 V
Reference potential for Safe ESDa and Safe ESDb
Safe STOP CLOSE
Digital input for Safe STOP function in direction CLOSE
0 V
Reference potential for Safe STOP CLOSE
Safe STOP OPEN
Digital input for Safe STOP function in direction OPEN
0 V
Reference potential for Safe STOP OPEN
SIL ready
NO contact of SIL fault signal
SIL failure
NC contact of SIL fault signal
Com.
Reference potential for SIL fault signal
Fault causes
Description
SIL
Thermal fault
Motor protection tripped
Torque fault
Torque fault in directions OPEN and/or CLOSE
Fault position feed-
Current position feedback is outside permissible range.
back
Phase failure
One phase of power supply is missing.
Controls are not supplied with mains voltage
Phase sequence
The phase conductors L1, L2 and L3 are connected in the wrong sequence.
fault
Power supply failure
The safety-related part of controls is without power supply.
Temperature fault
Temperature within actuator controls housing too high.
Failure of heating system for ambient temperatures below 25 °C
Failure of actuator
Actuator of valve locked
monitoring
Fault in redundant
Both signals Safe ESDa and Safe ESDb are not simultaneously on the same level.
wiring Safe ESD
Internal error
Internal error of the SIL module
18
The Safe STOP OPEN and Safe STOP CLOSE inputs are two independent inputs
with independent functions:
If Safe STOP OPEN = low level, the safety function inhibits operation in direction
OPEN (exception ESD OPEN)
If Safe STOP CLOSE = low level, the safety function inhibits operation in direc-
tion CLOSE (exception ESD CLOSE)
Permissible input voltage range:
High level: 15
30 V DC
Low level: max. 5 V DC
Signal behaviour of
SIL ready
SIL ready/ Absence of fault to be detected by diagnostics:
NO (NO contact) output = closed
NC (NC contact) output = open
SIL failure/ Presence of fault to be detected by diagnostics:
NO (NO contact) output = open
NC (NC contact) output = closed
SIL fault displayed via
SIL failure
For further information on SIL faults and in particular to assist in troubleshooting,
refer to chapter <Indications>.
Installation and commissioning must be recorded and a final installation and
commissioning report must be issued.
SA .1 with AC 01.2-22X/-22Y/ACExC 01.2-22X/-22Y
and
SIL failure
Customer connections for control
(typical assignment)
[1] Parallel
XK 31
XK 32
XK 33
XK 35
XK 37
XK 36
XK 38
XK 40
XK 39
XK 42
output
Multi-turn actuators
outputs:
[2] Fieldbus
XK 3
XK 5
XK 7
XK 8
XK 9
XK 10
XK 11
XK 15
XK 14
XK 16