SPECIFICATION
CSA Input (Natural Gas or Propane*) - MBH
CSA Input (Natural Gas or Propane*) - kW
CSA Output - MBH
CSA Output - kW
A.F.U.E.
Minimum gas supply pressure (Natural Gas or Pro-
pane) - inch w.c.
Maximum gas supply pressure (Natural Gas or
Propane) - inch w.c.
Power use (120Vac/60Hz) @ full fire - Watts (without
pumps)
Weight (empty) - lbs/Kg
Pressure vessel water content - USG/Litres
Maximum boiler flow rate - USgpm
Minimum boiler flow rate - USgpm
Maximum operating water pressure† - psig
Minimum water pressure - psig
Approved installation altitude - ASL
Ambient temperature - Low (°F-°C)
Ambient temperature - High (°F-°C)
Max. relative humidity (non-condensing)
Minimum water temp.
Maximum water temp. (electronic hi-limit)
Maximum water temp. lockout limit
Max. ΔT - supply/return (electronic fence)
Maximum equivalent vent length, each side (vent
and air intake
- 2"
(Natural Gas or Propane
-3"
Air intake options: either direct vent or indoor sup-
ply
INSTALLATION AND OPERATING INSTRUCTIONS
SL 10-85 G3, SL 14-115 G3, SL 20-160 G3, SL 30-199 G3 MODULATING GAS BOILERS
SPECIFICATIONS
SL 10-85 G3
10.6 - 85
3.10 - 24.9
10.1 - 79
2.96 - 23.1
96%
4
14
54
85 / 39
2.47 / 9.35
14
2
30
8
0 - 12,000'
32°F / 0°C
122°F / 50°C
90%
34°F / 1°C
190°F / 88°C
201°F / 94°C
40°F
100'
240'
SL 14-115 G3
SL 20-160 G3
14 - 115
20 - 160
4.10 - 33.7
5.86 - 46.9
13.3 - 109
19.0 - 147
3.90 - 32.0
5.57 - 43.1
95%
95%
4
4
14
14
72
82
102 / 46.3
85 / 39
1.72 / 6.51
2.47 / 9.35
14
19
2
4
30
30
8
8
0 - 12000'
0 - 12,000'
32°F / 0°C
32°F / 0°C
122°F / 50°C
122°F / 50°C
90%
90%
34°F / 1°C
34°F / 1°C
190°F / 88°C
190°F / 88°C
201°F / 94°C
201°F / 94°C
40°F
40°F
35'
100'
240'
170'
SL 30-199 G3
32 - 199
9.37 - 58.3
30 - 181.3
8.8 - 53.1
95%
4
14
100
152 / 69
5.09 / 19.3
22
6
30
8
0 - 12,000'
32°F / 0°C
122°F / 50°C
90%
34°F / 1°C
190°F / 88°C
201°F / 94°C
40°F
N/A
150'
3