SYMPTOM
TEMPERATURE SENSOR
ERROR
Touch Screen Message:
Error - Max. In-Out Temp. Exceed.
-> Check water flow
temperature signal not within
acceptable range. Potential flow
or sensor failure. Consult service
technician.
MISCELLANEOUS
Touch Screen Message:
Blank – screen dark, but fan
running Indicative of power-surge
damage to appliance
TROUBLESHOOTING
SL 20-115 G2 MODULATING GAS BOILER
SL 10-85 G3, SL 14-115 G3, SL 20-160 G3, SL 30-199 G3 MODULATING GAS BOILERS
DIAGNOSIS
Current outlet
temperature exceeds
operating limit.
Defective or
disconnected
Water
temperature sensor.
REMEDY
Check water flow.
Check wiring to temperature sensor and control
module.
Check temperature sensor. See Section 5.2.1.
Check transformer; replace if damaged.
Check circuit board for visible damage.
5-7