Midea MV5-X252W/V2GN1 Service Manual page 100

Commercial air conditioners
Table of Contents

Advertisement

... flowchart continued from previous page
No
Wires between DC filter board and
inverter module are loose
No
Wires from three-phase bridge rectifier
to reactor, DC filter board and/or AC
filter board are loose
No
The power supply is abnormal
No
Contactor is open
No
Replace three-phase bridge rectifier,
reactor and/or capacitor
Notes:
1.
Inverter module voltage monitor ports are ports CN36 and CN38 on the main PCB (labeled 22 and 21, respectively, in Figure 5-2.1 in Part 5, 2.2 "Ports").
The normal voltage between the +15V and N pins is 15V DC. Refer to Figure 5-4.19.
2.
Inverter module voltage monitor ports are ports CN36 and CN38 on the main PCB (labeled 22 and 21, respectively, in Figure 5-2.1 in Part 5, 2.2 "Ports").
The normal voltage between the P and N pins should be between 300V and 800V. Refer also to Figure 5-4.19.
Figure 5-4.19: Inverter module voltage monitor ports
CN36: Inverter module A
voltage monitor port
201608
Ensure the wires are
Yes
Ensure the wires are
Yes
connected properly
4
Yes
Yes
neutral terminals on
Wiring connections
300-800V
connected properly
Check the power
supply equipment
Voltage between
power output and
main PCB are
5
220±10%V AC
Yes
at contactor
terminals is(are)
loose
No
The contactor is
blocked
300-800V
15V
15V
V5 X VRF 50/60Hz
Replace
No
outdoor main
PCB
Ensure the
wires are
Yes
connected
properly
Replace the
Yes
contactor
CN38: Inverter module B
voltage monitor port
99