Midea MV5-X252W/V2GN1 Service Manual page 44

Commercial air conditioners
Table of Contents

Advertisement

2 Outdoor Unit Main PCB
2.1 Types
There are four main PCB types for V5 X outdoor units. 8/10/12HP units share a main PCB type, 14/16HP share a main PCB
type, 18HP has a unique main PCB type, and 20/22HP share a main PCB type. The type label is affixed to the main PCB.
When changing a main PCB, be sure to use the right type of main PCB. Refer to Table 5-2.1.
Table 5-2.1: Main PCB type labels
Capacity
8/10/12HP
Label
Notes:
1.
The 20/22HP main PCB can also be used on 8/10/12HP units. The only difference is that the 20/22HP main PCB has two inverter modules whilst the
8/10/12HP main PCB has one inverter module. If a 20/22HP main PCB is used on an 8/10/12HP unit, the unit will run normally but LED6 will flash and LED7
will be continuously on.
2.2 Ports
Figure 5-2.1: Outdoor unit main PCB ports
Notes:
1.
Label descriptions are given in Table 5-2.2.
201608
14/16HP
1
V5 X VRF 50/60Hz
18HP
1
20/22HP
Instruction
Type label
label
43