Midea MV5-X252W/V2GN1 Service Manual page 29

Commercial air conditioners
Table of Contents

Advertisement

V5 X VRF 50/60Hz
5.5 Electronic Expansion Valve Control
The positions of electronic expansion valves EXVA and EXVB are controlled in steps from 0 (fully closed) to 480 (fully
open).
In cooling mode:
 When all outdoor units are in standby:
 All EXVs are at position 352 (steps).
 When some outdoor units are running and some outdoor units are in standby:
 EXVs on running outdoor units are controlled according to discharge temperature. EXVs of units in standby are
fully closed.
 When all outdoor units are running:
 All EXVs are controlled according to discharge temperature.
In heating mode:
 When all outdoor units are in standby:
 All EXVs are at position 352 (steps).
 When some outdoor units are running and some outdoor units are in standby:
 EXVs on running outdoor units are controlled according to discharge superheat. EXVs of units in standby are fully
closed.
 When all outdoor units are running:
 All EXVs are controlled according to discharge superheat.
28
No. 1
No. 2
No. 3
No. 7
No. 8
No. 1
No. 5
No. 6
No. 7
No. 3
No. 4
No. 5
BP1
BP2
BP1
No. 4
No. 5
No. 6
No. 2
No. 3
No. 4
No. 8
No. 1
No. 2
No. 6
No. 7
No. 8
BP2
BP1
BP2
No. 7
No. 8
No. 5
No. 6
No. 3
No. 4
No. 1
No. 2
BP1
BP2
201608