4.22 PP, F0 Troubleshooting
4.22.1
Digital display output
4.22.2
Description
PP indicates compressor discharge insufficient superheat protection. When the discharge gas superheat is ≤0°C for 20
minutes or ≤5°C for 60 minutes, the system displays PP protection and all units stop running.
F0 indicates PP protection has occurred 3 times in 150 minutes. When an F0 error occurs, a manual system restart is
required before the system can resume operation.
Error code is only displayed on the unit with the error.
4.22.3
Possible causes
Temperature sensor not connected properly or has malfunctioned.
Poor temperature sensor heat insulation.
Excess refrigerant.
Discharge pressure too high.
Main PCB damaged.