Simplex 2004 Series Operation Manual page 20

Fire alarm control unit
Hide thumbs Also See for 2004 Series:
Table of Contents

Advertisement

Options
Settings
Use the Active Status Reminder option to set an
interval and duration during which the system
piezo reminds operators that a FIRE, SUPV, or
TBL condition still exists.
This is accomplished by sounding the front
control unit tone-alert as well as flashing the
Active Status
LEDs for respective events.
Reminder
Choose ON or OFF. The default is ON.
If you choose ON, the reminder interval is set to
eight hours.
Signal duration on until ACK; means
acknowledge is required to silence the reminder.
While the timer is counting down, the Alarm
Silence/Reset Inhibit Timer prevents a system
operator from using either the Alarm Silence or
System Reset functions.
Alarm Silence/
When the inhibit timer expires, the system
Reset Inhibit
operator can silence or reset the control unit.
Choose ON or OFF. The default is OFF.
If you choose ON, inhibit timer is set to one
minute.
Use the Alarm Signal Cutout timer to set a
duration for how long notification appliances
sound after an alarm.
Alarm Cutout
Timer
Choose ON or OFF. The default is OFF.
If you choose ON, the NAC silences after 20
minutes.
Choose ON or OFF. The default is OFF.
This option enables communication with
Enable
annunciators.
Annunciator
If you enable an annunciator but you do not
connect an annunciator to the control unit, the
system reports a trouble.
Choose ON or OFF. The default is OFF.
If you set this option to ON, both horns and
strobes connected on the QALERT NACs turn off
NFPA NAC
when you activate alarm silence.
If you set this option to OFF, strobes turn off
after the completion of a system reset.
page 18
2004 Foundation Series Fire Alarm Control Unit Operation Guide
Table 14: System options setting
Options
Depleted
Battery Cutout
Enable City
Circuit
Disconnect
DACT
AHJ Reset
Feature
Cold Start /
Warm Start
Settings
Choose ON or OFF (default = OFF).
This option selects the operation of the control unit
if an alarm occurs during an AC power loss while a
depleted battery trouble exists.
If this option is selected, the system does the
following:
• An alarm does not initiate if the first alarm occurs
after the depleted battery state has been detected.
If the hardware jumper for depleted battery cutout
has been clipped, the system shuts down 60
seconds after the depleted battery condition is
detected.
• An alarm continues to sound if the depleted battery
state is reached after the system is already in the
alarm state.
Choose ON or OFF (default = OFF).
This option activates the control unit's city circuit
module.
If you use a city circuit in the system, you must select
this option or the system reports a trouble.
If you select this option and you do not connect the
city module, the system reports a trouble.
There is no other programming required for the city
module.
The city type is configured with jumpers on the city
circuit board.
Choose ON or OFF. The default setting is OFF.
If you choose ON, it disconnects the DACT and causes
a trouble.
Choose ON or OFF. The default setting is OFF.
When set to ON, the system resets if the current state
of a device or point no longer causes an alarm. For
example, the system resets if a device or circuit is in a
Trouble state.
When set to OFF, the system resets only if the current
state of a device or point is normal.
Choose ON or OFF. The default is OFF.
Off – Warm start; On – Cold start.
This option sets the power cycle of the control unit.
579-1403 Rev A

Advertisement

Table of Contents
loading

Table of Contents