Toshiba HWT-602S21SM3W-E(TR) Service Manual page 247

Air to water heat pump
Table of Contents

Advertisement

Exchange
No.
parts name
2. Attachment
Compressor
and
1) Attach the compressor in the reverse process of
compressor
"1. Detachment".
lead
(continued)
• Also ensure to replace the compressor lead
• Install the sound insulation board (inner and
3. Vacuum
1) Connect the vacuum pump to the charge port of the
liquid and gas pipe valves and the check joint on the
high pressure side, and then operate the vacuum
pump.
2) Vacuum until the vacuum low pressure gauge reaches
1 (mmHg).
NOTE
Fully open the electronic control valve before the vacuum
process. If closed the vacuum pipe between the liquid
pipe valve and electronic control valve of the outdoor unit
may not be able to be drawn through.
Method for forcibly fully opening the electronic control valve
• Turn on the power supply breaker.
• Ensure that D805 of the LED indication of the outdoor is
lit up. If D805 is not lit up (off or flashing) then push and
hold down SW01 and SW02 at the same time for at
least 5 seconds and check that D805 lights up.
• Push and hold SW01 down for at least 5 seconds or to
confirm that D804 is slowly flashing (once/second).
• Push SW01 several times until the LED
indications (D800 to D804) become the following.
D800
: Go ON,
• Push SW02 and D805 will start rapidly flashing.
• Push and hold SW02 down for at least 5 seconds and
D804 will start slowly flashing.
Once D805 lights up the PMV will start to open.
After 30 seconds turn off the power breaker.
4. Refrigerant encapsulation
1) Add the amount of refrigerant determined by the pipe
length using the charge port of the valve.
Work procedure
after replacing the compressor.
outer) through the space between the
compressor and the piping, and between the
pipes and separate plate as shown on the right.
D801
D802
: Go OFF,
: flash (5 times/sec.)
LED indicator
LED indicator
D800-D805
D800-D805
SW01 SW02
SW01
Pull out the compressor lead
Pull out the compressor lead
and compressor case thermostat
and compressor case thermostat
lead from this gap.
lead from this gap.
D803
D804
Push redundant compressor lead,
Push redundant compressor lead,
compressor case thermostat lead into a
compressor case thermostat lead into a
clearance between sound insulation board
clearance between sound insulation board
(inner) and sound insulation board (outer).
(inner) and sound insulation board (outer).
Pull out the compressor lead,
Pull out the compressor lead,
the compressor case thermostat lead
the compressor case thermostat lead
from the gap of the sound insulation
from the gap of the sound insulation
SW02
Push the sound insulation plate (inner and
Push the sound insulation plate (inner and
upper) into the inside of the sound insulation
upper) into the inside of the sound insulation
(outer) securely so that there is no clearance
(outer) securely so that there is no clearance
between sound insulation (upper) and sound
between sound insulation (upper) and sound
insulation(outer)
insulation(outer)
246
Remarks
Ferrite core
Ferrite core
Wrap the seam of the sound insulation
Wrap the seam of the sound insulation
(inner) and sound insulation (outer) about
(inner) and sound insulation (outer) about
this position.
this position.