Item
7-4.
4) Outdoor fan control
Outdoor unit
The outdoor side control part controls the number of fan motor rotations by receiving an operation instruction from the
control
Hydro side (Hydro unit) control part.
For sensing the true outside temperature, fan is operated without compressor operation.
* Although the fan motor is a DC motor, which has non-step variable numbers of rotations, it is limited to some steps for convenience of
control.
The number of fan tap rotation allocation [rpm]
Single phase
outdoor unit
401, 601
801, 1101
1401
3 phase
outdoor unit
801, 1101, 1401
4-1) Cooling fan control
• The TL sensor, TO sensor and operation frequency control the outdoor fan. The control is performed by 1 tap of
the DC fan control (14 taps).
• For 60 seconds after the start, the maximum fan tap for each zone that is shown in the following table is fixed. After
that, the fan is controlled according to the TL sensor (401, 601), TG (801,1101,1401). (TG: temperature converted
from PD)
Single phase outdoor unit 401, 601
TL [ °C]
56
53
+ 1 tap / 20 secs
(Up to the maximum number of rotation for each zone)
38
Number of rotation hold
35
- 1 tap / 20 secs
(Up to the minimum number of rotation for each zone)
Temperature range
29°C ≤ TO < 38°C
15°C ≤ TO < 29°C
5°C ≤ TO < 15°C
Single phase outdoor unit 801, 1101
TG [°C]
58
55
+ 1 tap / 20 secs
(Up to the maximum number of rotation for each zone)
38
Number of rotation hold
35
Temperature range
29°C ≤ TO < 38°C
15°C ≤ TO < 29°C
5°C ≤ TO < 15°C
Operation flow and applicable data, etc.
W1
W2
W3
240
320
320
200
200
200
200
200
200
W1
W2
W3
200
200
200
WF tap
Less than 20 Hz
Minimum
Maximum
38°C ≤ TO
W6
W5
W4
W3
WF tap
- 1 tap / 20 secs
(Up to the minimum number of rotation for each zone)
Less than 20 Hz
Minimum
Maximum
38°C ≤ TO
W6
W5
W4
W3
W4
W5
W6
W7
W8
390
400
470
510
550
230
260
290
330
360
200
230
290
370
450
W4
W5
W6
W7
W8
200
230
290
370
450
20 Hz or more to less
than 45 Hz
Minimum
Maximum
WC
W8
WF
WB
W7
WD
W8
W6
WA
W6
W5
W8
20 Hz or more to less
than 45 Hz
Minimum
Maximum
WC
W8
WF
WB
W7
WD
W8
W6
WA
W6
W5
W8
101
W9
WA
WB
WC
WD
560
570
570
650
700
410
450
480
500
540
490
550
600
660
720
W9
WA
WB
WC
WD
490
550
600
660
720
45 Hz or more
Minimum
Maximum
WA
WF
W9
WD
W8
WC
W7
WA
45 Hz or more
Minimum
Maximum
WA
WF
W9
WD
W8
WC
W7
WA
WE
WF
750
830
570
600
760
800
WE
WF
760
800