Summary Table Setting Values; Modbus Communication System Integration; Basic Features Of Modbus-Rtu Control; Modbus Memory Map - S&P CTB ECOWATT PLUS Manual

Ventilation unit
Table of Contents

Advertisement

Available languages

Available languages

7.3. SUMMARY TABLE SETTING VALUES

Registro
T1
T2
T3
Period T1
Period T2
Period T3
Set T1
Set T2
Set T3
Date start
Hour start
Date end
Hour end
Set Holidays

8. MODBUS COMMUNICATION SYSTEM INTEGRATION

8.1. BASIC FEATURES OF MODBUS-RTU CONTROL

Addressing
Diffusion
Transmissions speed
Parity
Mode
Electrical interface
Connector type
MODBUS message
Direction
Function
8 bits
8 bits
Format for each byte in RTU mode is:
• System codes: 8–bit binary
• Bits per Byte: 1 bit to START (start)
8 bits for data, the most signifi cant bit is sent fi rst
1 bit for parity (Even parity is required)
1 bit for STOP (end)

8.2. MODBUS MEMORY MAP

Holding registers
N°REG.
Register
0
TipoMotor
1
ModoFun
Min.
Max.
Description
OFF
23:59
Start time period frame
0min
480min
Period frame duration
OFF
100%
Percentage over set point
00:00
23:59
Starting date holidays period
00:00
23:59
Starting hour holidays period
00:00
23:59
Ending date holidays period
00:00
23:59
Ending hours holidays period
OFF
100%
Percentage over the set point for holidays period
Slave: confi gurable address from 1 to 247
Yes
9600 (19200 is recommended too)
PAR/EVEN
RTU
RS485 2W-wired or RS232
RJ 45
Dates
CRC verifi cation
N x 8bits
16 bits
Min.
Max.
0
1
0=PI_Presión
1=PI_Caudal
2=Proporcional
0
7
4=PI_Presión+RTC
5=PI_Caudal+RTC
6=Proporcional+RTC
7=Max-Min+RTC
Master: able to adress slaves with address from 1 to 247
Description
Default
0=AC
1
1=DC
3=Max-Min
0
Comments
Motor type
Operation mode
59
EN

Advertisement

Table of Contents
loading

This manual is also suitable for:

Crhb-n ecowatt plusCrvb-n ecowatt plus

Table of Contents