Convenience Receptacle (Field Powered)

A Ground Fault Circuit Interrupter (GFCI) convenience
receptacle is provided in the main control box on all units. To
use this receptacle, connect a separate field-supplied 115 V
power wiring circuit to the outlet.
Figure 94: Unit Powered GFCI Receptacle Schematic
www.DaikinApplied.com

Convenience Receptacle (Unit Powered)

A Ground Fault Circuit Interrupter (GFCI) convenience
receptacle is provided in the main control box on all units. The
receptacle shall be powered by a factory installed and wired
120V, 20 amp power supply. The power supply shall be wired
to the line side of the unit's main disconnect, so the receptacle
is powered when the main unit disconnect is off. This option
shall include a GFI receptacle, transformer, and a branch
circuit disconnect. The electrical circuit shall be complete with
primary and secondary overload protection. See
a branch circuit diagram.