Daikin Rebel DPS Series Installation And Maintenance Manual page 21

Commercial packaged rooftop systems
Table of Contents

Advertisement

Table 8: DPS 003–015 Electric Heat Data
KW
6
12
18
30
36
54
72
NOTE: 1. Maximum temperature rise equals 60ºF
www.DaikinApplied.com
1
Voltage
Amps
208
16 .7
240
14 .4
480
7 .2
208
33 .3
240
28.9
480
14 .4
208
50.0
240
43 .3
480
21 .7
600
17 .3
208
83.3
240
72 .2
480
36 .1
600
28.9
208
99 .9
240
86.6
480
43 .3
600
34 .6
208
149 .9
240
129 .9
480
65.0
600
52.0
208
199 .9
240
173 .2
480
86.6
600
69 .3
Table 9: DPS 016–028 Electric Heat Data
KW
10
20
30
45
60
72
90
120
150
NOTE: 1. Maximum temperature rise equals 60ºF
21
Electrical Installation
1
Voltage
Amps
208
27.8
240
24 .1
480
12.0
600
9 .6
208
55 .5
240
48.1
480
24 .1
600
19 .2
208
83.3
240
72 .2
480
36 .1
600
28.9
208
124 .9
240
108.3
480
54 .1
600
43 .3
208
166 .5
240
144 .3
480
72 .2
600
57 .7
208
199 .9
240
173 .2
480
86.6
600
69 .3
208
249.8
240
216 .5
480
108.3
600
86.6
480
144 .3
600
115 .5
480
180.4
600
144 .3
IM 1125-13 • REBEL ROOFTOPS