Figure 114: Optional Outdoor Air Monitor – Set Up Menu
Press and release ↑/↓ during normal operation to select
Enter (Move →)
Esc (Normal Operation)
IP/SI Units ↓
Set Up ↓↑
Visible only when LCD U/M=CFM
LCD1 U/M=FPM ↓
1
Set LCD1 Units?
LCD1 U/M=FPM ↓
Displays airflow in FPM.
affects the LCD display reading
and output when set for CFM.
LCD1 U/M=CPM ↑
Displays airflow in CFM (User
must input AR1 area .
IM-1125-13 • REBEL ROOFTOPS
Enter (Move →)
Esc (Move ←)
See
Figure 110:
System
Units Menu,
page 146
AR1=0.000 SQF ↓↑
OUT1 U/M=FPM ↓↑
1
1
Set Area1?
AR1=0.00SQF ↑
Set area between
Outputs airflow in FPM.
0.00 and 999.99 sq.ft. Area
OUT1 U/M=CPM ↑
Outputs airflow in CFM (User
Appendix - Keypad Display Menu Structure
Enter (Move →)
Esc (Move ←)
OUT1=4-20mA ↓↑
1
Set Out1 Units?
OUT1 U/M=FPM ↓
OUT1=0–10V ↓
2
In addition, "SW1" must be set
to the VDC position to change
airflow output to 0–10VDC.
OUT1=0–5V ↓↑
2
In addition, "SW1" must be set
to the VDC position to change
must input AR1 area .
airflow output to 0–5VDC.
OUT1=4–20mA ↑
2
In addition, "SW1" must be set to
the mA position to change airflow
output to 4–20mA.
150
Enter (Action, Move →→)
Esc (Move ←←)
FS1 units determined by
OUT1 U/M setting
FS1=5000FPM ↓↑
1
FS1=10000FPM for GF1
1
FS1=5000CFM ↓↑
1
FS1=10000CFM for GF1
1
Set Out1?
Set FS1?
2
FS1=5000FPM ↓↑
FS1=10000FPM for GF1
FS1=5000CFM ↓↑
FS1=10000CFM for GF1
Fullscale analog output value
from 100 to 15,000 for FPM
(up to 999,999 for CFM) in
increments of 1.
Value must be ≥ LL1 + 10 or, if
LL1=0, value must be ≥ 100.