Daikin Rebel DPS Series Installation And Maintenance Manual page 52

Commercial packaged rooftop systems
Table of Contents

Advertisement

High Fire Setting – Button 1
To enter the high fire setting mode, press and hold button #1
until the LED lights solid red. Release. The valve is now in
the high fire setting mode. Buttons #1 and #2 are used to set
desired high fire settings.
Press or hold button #1 to increase gas flow. Each button press
equates to the minimum available step size and will increase
flow slowly. Holding the button down auto-steps and eliminates
the need to repeatedly press the button. Use this feature to
rapidly increase the flow.
Press or hold button #2 to decrease gas flow. Each button
press equates to the minimum available step size and will
decrease flow slowly. Holding the button down auto-steps and
eliminates the need to repeatedly press the button. Use this
feature to rapidly decrease the flow.
To save the high fire setting, simultaneously hold buttons #1
and #2 until the LED turns OFF.
NOTE: Controls left in any setting mode will default to the
current setting and return to normal operating mode
after 5 minutes of inactivity.
Table 17: Capacity of Pipe Natural Gas (CFH)
Pipe Length (ft .)
½
10
132
20
92
30
73
40
63
50
56
60
50
70
46
80
53
90
40
100
38
125
34
150
31
175
28
200
26
NOTE: Use multiplier below for other gravities and pressure drops.
Table 18: Specific Gravity Other Than 0.60
Specific Gravity
0.50
0.60
0.70
0.80
0.90
1.00
PROPANE-AIR
1.10
1 .55
2.00
IM-1125-13 • REBEL ROOFTOPS
With Pressure Drop of 0 .3" Wc & Specific Gravity Of 0.60
¾
1
278
520
190
350
152
285
130
245
115
215
105
195
96
180
90
170
84
160
79
150
72
130
64
120
59
110
55
100
Multiplier
1.100
1.000
0.936
0.867
0.816
0.775
0.740
PROPANE
0.622
BUTANE
0.547
Low Fire Setting – Button 2
To enter the high fire setting mode, press and hold button #2
until the LED lights solid red. Release. The valve is now in
the high fire setting mode. Buttons #1 and #2 are used to set
desired high fire settings.
Press or hold button #2 to decrease gas flow. Each button
press equates to the minimum available step size and will
decrease flow slowly. Holding the button down auto-steps and
eliminates the need to repeatedly press the button. Use this
feature to rapidly decrease the flow.
Press or hold button #1 to increase gas flow. Each button press
equates to the minimum available step size and will increase
flow slowly. Holding the button down auto-steps and eliminates
the need to repeatedly press the button. Use this feature to
rapidly increase the flow.
To save the high fire setting, simultaneously hold buttons #1
and #2 until the LED turns OFF.
NOTE: Controls left in any setting mode will default to the
current setting and return to normal operating mode
after 5 minutes of inactivity.
Pipe Size-inches (Ips)
2
1050
1600
2050
730
1100
2100
590
890
1650
500
760
1450
440
670
1270
400
610
1150
370
560
1050
350
530
990
320
490
930
305
460
870
275
410
780
250
380
710
225
350
650
210
320
610
Table 19: Pressure Drop Other Than 0.3"
Pressure Drop
Multiplier
0.1
0.2
0.3
0.4
0.6
0.8
52
Optional Gas Heat
3
4800
8500
3300
5900
2700
4700
2300
4100
2000
3600
1850
3250
1700
3000
1600
2800
1500
2600
1400
2500
1250
2200
1130
2000
1050
1850
980
1700
Pressure
0.577
1.0
0.815
2.0
1.000
3.0
1 .16
4.0
1 .42
6.0
1 .64
8.0
www.DaikinApplied.com
4
17500
12000
9700
8300
7400
6800
6200
5800
5400
5100
4500
4100
3800
3500
Multiplier
1.83
2.58
3 .16
3 .65
4 .47
5 .15