Installation; Installation Codes; Clearances - Raypak 406A Installation And Operation Manual

Gas-fired pool and spa heater, bronze asme and polymer atmospheric heat exchanger
Table of Contents

Advertisement

4. INSTALLATION

A
WARNING: This unit contains refractory ceramic
fiber (RCF) insulation in the combustion chamber. RCF,
as manufactured, does not contain respirable crystalline
silica. However, following sustained exposure to very
high temperatures (>2192°F), the RCF can transform
into crystalline silica (cristabolite). The International
Agency for Research on Cancer (IARC) has classified
the inhalation of crystalline silica (cristabolite) as
carcinogenic to humans.
When removing the burners or heat exchangers, take
precautions to avoid creating airborne dust and avoid
inhaling airborne fibers. When cleaning spills, use wet
sweeping or High Efficiency Particulate Air (HEPA)
filtered vacuum to minimize airborne dust. Use feasible
engineering controls such as local exhaust ventilation
or dust collecting systems to minimize airborne dust.
Wear
appropriate
personal
including gloves, safety glasses with side shields, and
appropriate
NIOSH-certified
to avoid inhalation of airborne dust and airborne fiber
particles.
IMPORTANT NOTICE: These instructions are intended
only for the use by qualified personnel, specifically
trained and experienced in the installation of this type
of heating equipment and related system components.
Installation and service personnel may be required by
some states to be licensed. If your state is such, be sure
your contractor bears the appropriate license. Persons
not qualified shall not attempt to fix the equipment nor
attempt repairs according to these instructions.
WARNING:
A
Improper
alteration, service or maintenance may damage the
equipment, creating a hazard resulting in asphyxiation,
explosion or fire. Such damage is not covered under
warranty.
NOTE: The heater should not be located in an area
where possible water leakage will result in damage to
the area adjacent to the heater or to the structure. When
such locations cannot be avoided, it is recommended
that a suitable drain pan, with adequate drainage, be
installed under the heater. The pan must not restrict
combustion air flow.
RECOMMENDATION: For regions with snow, Raypak
recommends installing these units indoors.
PRELIMINARY
protective
equipment
respiratory
protection,
installation,
adjustment,
UNCONTROLLED DOCUMENT IF PRINTED

Installation Codes

Installation must be in accordance with local codes, or,
in the absence of local codes, with the latest edition of
the National Fuel Gas Code, ANSI Z223.1/NFPA54 and
National Electrical Code, ANSI/NFPA 70, and for Canada,
the latest edition of CAN/CSA-B149 Installation Codes,
and Canadian Electrical Code, CSA C22.1 Part 1 and
Part 2.

Clearances

All Heaters
For indoor and outdoor clearances from combustible
surfaces, see the chart below.
Location
Top *
30" (762 mm) Drafthood
Front
Alcove (Open)
Vent
6" (152 mm)
Floor **
0"
Back
6" (152 mm)
Right Side
12" (305 mm) Water Side
Left Side
6" (152 mm) Opposite Water Side
Location
Top *
Unobstructed (Outdoor Stack)
Top ***
36" (914 mm) (Stackless Top)
Floor
0"
Back
6" (152 mm)
Right Side
12" (305 mm) Water Side
Left Side
6" (152 mm) Opposite Water Side
* Clearance from top of vent terminal
** Do not install on carpeting
*** Clearance from top of heater
Table B.
Minimum Clearances from Combustible Surfaces
Indoor Installation
Outdoor Installation
7