A Series Inverter Modular Air-cooled Chiller (Heat Pump)
Symptoms
Failed diischarge
temperature sensor

8.2 After-sales service

When the unit in warranty has a quality issue or fails to operate properly under the allowable operation
condition, please contact the local sales representative for free service.
The user is required to designate personnel to take charge of the unit following the instructions covered
in this manual, otherwise any maintenance cost caused by the improper operation will be at the user's
expense.
Probable causes
1. Too low water temperature.
2. The discharge temperature sensor
fell off.
45
Recommended action
1. Decrease the load to improve
the water temperature.
2. Check if the discharge
temperature sensor installed
correctly.