The cable should be fixed
by these three fasteners
The thru-hole after wiring
should be sealed to prevent
insects from entering.
The thru-hole after wiring
should be sealed to prevent
insects from entering.
The cable should be
fixed with fasteners.
(4) The unit shall be grounded reliably and never connect the ground wire with the gas fuel pipe, water
pipe, lightening rod or telephone line.
(5) After wiring, O-rings should be tightened to prevent coming of insects.
■ Control line
(1) The field supplied control line shall be at a minimum 1mm
(2) The electric box will send the control signal (220V AC, 5A) to control the chilled water pump and
auxiliary electric heater, however, never do not drive them directly through the control signal but
through their AC contactors.
(3) Switching signals (220V AC, 2A) for the running and error indicators are available for the electric
box.