4.5.2 Additional refrigerant charging

Outdoor unit has been charged refrigerant before delivery.
Charge additional refrigerant for field-installed connecting pipe. If the pipeline is longer than
1m(39-3/8inch), please refer to the following table for charging amount of refrigerant (Liquid pipe
prevails).
How much additional refrigerant should be charged.
Total refrigerant charging amount R= Pipeline charging amount A + ∑charging amount B of every
module.
(1) Pipeline charging amount
Added refrigerant quantity A for piping = ∑Liquid pipe length × Added refrigerant quantity for each
meter(inch) of liquid pipe.
28.6(1-1/8)
kg/m
0.680
OZ/inch
0.61
25.4(1)
22.2(7/8)
0.520
0.350
0.47
0.31
Fig.4.5.1
Fig.4.5.2
Diameter of liquid pipe
19.05(3/4)
15.9(5/8)
0.250
0.170
0.22
0.15
25
GMV DC Inverter VRF
12.7(1/2)
9.52(3/8)
0.110
0.054
0.10
0.05
mm(inch)
6.35(1/4)
0.022
0.02