When the distance between outdoor units exceeds 2m(6-1/2ft.), U-type oil trap
should be added at low pressure gas pipe. a+c≤10m(32-7/8ft.);b+c≤10m(32-7/8ft.);d≤10m (32-7/8ft.).
4.3.5 Fitting pipe between Outdoor Unit and the First Manifold
4.3.5.1 For single module system, pipe size (between outdoor unit and the first manifold) is
determined by that of outdoor unit.
Pipe size of basic outdoor module is shown as follows:
Basic Module
GMV-72WM/B-U(U)
GMV-96WM/B-U(U)
GMV-120WM/B-U(U)
Fig.4.3.6
Fig.4.3.7
Pipe between ODU and the first branch of IDU
Gas Pipe mm(inch)
Φ19.05(3/4)
Φ22.2(7/8)
Φ28.6(1-1/8)
15
GMV DC Inverter VRF
Liquid Pipe mm(inch)
Φ9.52(3/8)
Φ9.52(3/8)
Φ12.7(1/2)