4.3.5.6 Fitting pipe between manifolds
Pipe size (between two manifolds at indoor unit side) is based on the total capacity of upstream
indoor unit(s).
Total capacity of downstream indoor
unit(s) C(Btu/h)
C≤17100
17100<C≤48500
48500<C≤72000
72000<C≤96000
96000<C≤144000
144000<C≤216000
216000<C≤240000
240000<C≤336000
336000<C
4.3.5.7 Fitting pipe between indoor unit and manifold
Manifold should be matched with fitting pipe of indoor unit.
Rated capacity of indoor unit C(Btu/h)
C≤9500
9500<C≤17100
17100<C≤48500
48500<C≤72000
72000<C
Fig.4.3.13
Dimension of the pipe of indoor branch
Gas Pipe mm(inch)
Φ12.7(1/2)
Φ15.9(5/8)
Φ19.05(3/4)
Φ22.2(7/8)
Φ28.6(1-1/8)
Φ28.6(1-1/8)
Φ34.9(1-3/8)
Φ34.9(1-3/8)
Φ41.3(1-5/8)
Fig.4.3.14
Pipe between indoor branch and IDU
Gas Pipe mm(inch)
Φ9.52(3/8)
Φ12.7(1/2)
Φ15.9(5/8)
Φ19.05(3/4)
Φ22.2(7/8)
19
GMV DC Inverter VRF
Liquid Pipe mm(inch)
Φ6.35(1/4)
Φ9.52(3/8)
Φ9.52(3/8)
Φ9.52(3/8)
Φ12.7(1/2)
Φ15.9(5/8)
Φ15.9(5/8)
Φ19.05(3/4)
Φ19.05(3/4)
Liquid Pipe mm(inch)
Φ6.35(1/4)
Φ6.35(1/4)
Φ9.52(3/8)
Φ9.52(3/8)
Φ9.52(3/8)