Gree GMV-72WM/B-U Owner's Manual page 52

Hide thumbs Also See for GMV-72WM/B-U:
Table of Contents

Advertisement

GMV DC Inverter VRF
——
Debugging code Progress code
Progress
Code
db
db
db
15_Cooling
debugging
db
db
B If heating mode is selected, relevant display is as below:
——
Debugging code Progress code
Progress
Code
db
db
db
16_Heating
debugging
db
db
Step 18: if there's no error during operation for about 40min, system will automatically confirm
that debugging is finished and then stop. System resumes standby condition and displays as below:
——
Debugging code
Progress
Code
17_Debugging
01-04
finished
Step 19: after debugging is finished, some functions can be set up according to project's actual
needs. For specific details, please refer to System Functions Setup. If no special requirements, skip
this step.
LED1
LED2
Display
Display
code
status
status
Light
15
Light
Light
15
Light
Light
15
Light
Light
15
Light
Light
15
Light
LED1
LED2
Display
Display
code
status
status
Light
16
Light
Light
16
Light
Light
16
Light
Light
16
Light
Light
16
Light
Progress code
LED1
LED2
Display
Display
code
status
status
Light
OF
Light
Status code
LED3
Display
Code
status
Debugging is enabled in cooling mode
AC
Light
(debugging mode, auto-selected by
system).
Error
Error occurs during debugging in cooling
Light
code
mode.
Error of other modules occurs during
J0
Light
debugging in cooling mode.
Outdoor pipeline and valves are not
U9
Light
normal.
System detects error in indoor pipeline.
XXXX is the project no. of the faulted
IDU. 3s later, error code U8 is displayed.
XXXX/U8
Light
For example, IDU no. 100 has U8 error,
then LED3 displays like this: 01 (2s
later) 00 (2s later) U8, and repeat again.
Status code
LED3
Display
Code
status
Debugging is enabled in heating mode
AE
Light
(debugging mode, auto-selected by
system).
Error
Error occurs during debugging in
Light
code
heating mode.
Error of other modules occurs during
J0
Light
debugging in heating mode.
Outdoor pipeline and valves are not
U9
Light
normal.
System detects error in indoor pipeline.
XXXX is the project no. of the faulted
IDU. 3s later, error code U8 is displayed.
XXXX/U8
Light
For example, IDU no. 100 has U8 error,
then LED3 displays like this: 01 (2s
later) 00 (2s later) U8, and repeat again.
Status code
LED3
Display
Code
status
Debugging is finished. System is on
OF
Light
standby condition. LED1 displays module
address. LED2 and LED3 display "OF".
48