DESCRIPTION OF THE UNIT

AIM OF THE UNIT
The fan coil is a room air treatment terminal unit for both winter and summer operation.
Versions Omnia HL_N
A fan coil with cabinet, for universal installation and fitted with a multifunction electronic thermostat. It can be installed as an
autonomous unit or within a network: it can, in fact, manage a network of a further 5 fan coils*.
* The fan coils within a network must be pre-arranged models, or equipped with the special accessories.
• Omnia HL_N, RAL 9002 white casing; head and feet, RAL7044
TECHNICAL DATA AND OPERATING LIMITS
Thermal capacity (maximum) (input water 70°C)
Cooling output (maximum) (input water 7°C)
Power consumed (maximum)
Current consumed (maximum)
Input water temperature (maximum)
Operating pressure (maximum)
Room temperature limits Ta
Relative humidity limits in the room R.H.
Protection rating
Power supply
Performance values refer to the following conditions:
- at the maximum motor speed;
Water temperature
In order to prevent air stratification in the
room, and therefore to achieve improved
mixing, it is advisable not to supply the
fan coil with water at a temperature over
65°C.
Minimum average water temperature
If the fan coil is working in continuous
cooling mode in an environment where
the relative humidity is high, condensate
might form on the air delivery and on the
outside of the device. This condensate
might be deposited on any objects
Minimum average water temperature [°C]
Temperature with wet bulb
of the air in the room
HL
[W]
[W]
[W]
[A]
[°C]
[bar]
IP
[V~Hz]
- the total input power is determined by adding the input power for the
unit and the input power for the accessories connected and declared in
the corresponding manuals.
The use of water at high temperatures
could cause squeaking due to the
different thermal expansions of the
elements (plastic and metal), this does
not however cause damage to the unit if
the maximum operating temperature is
underneath and on the floor.
To avoid condensate on the external
structure of the device while the fan is
functioning, the average temperature of
the water must not be lower than the
limits shown in the table below, that
depend on the thermo-hygrometric
21
15
17
19
21
23
16 N / NM
26 N / NM
2910
4620
1200
2030
32
35
0,15
0,18
80
8
0°C < Ta < 40°C
U.R. < 85%
20
230V ( ±10% ) ~ 50Hz
not exceeded.
conditions of the air in the room.
These limits refer to unit operating with
fan at minimum speed.
Temperature of the air in the room with dry bulb
23
25
3
3
3
3
3
3
3
3
3
6
5
4
-
8
7
IHLNLJ 2302 - C6887213_01
26 N / NM
5940
2830
42
0,22
27
29
31
3
3
3
3
3
3
3
3
3
3
3
3
6
5
5
29

Advertisement

loading

This manual is also suitable for:

Omnia hl 16 nOmnia hl 26 nOmnia hl 36 n