Heat Pump Appliances - Olimpia splendid ARYAL S1 E 10 C Instructions For Use And Maintenance Manual

Inverter
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 45
For assembly, follow the relative instructions, attached to the kit packaging, scrupulously.
f. The unit must not be in a position that obstructs the passage of persons or animals.
g. The unit should not be installed downwind of chimneys discharging burnt gas or subject to emissions of
fumes, oily or corrosive gasses.
h. It should be possible to discharge the condensation produced.
i. Take the air conditioner weight into account and select a place where noise and vibration will not be an
issue.
l. Select a place so that the warm air and noise from the air conditioner do not disturb neighbors.
m. Zones with probable accumulation of snow (figure 13).
Position the outdoor unit on a raised surface (wall), with height above the foreseeable maximum amount
of snowfall, since:
• if the appliance does not have a heat pump, when the snow melts, water may infiltrate inside the unit
and cause damage to the electric components.
• if the appliance has a heat pump, the accumulation of snow prevents the regular circulation of the air
and makes condensate drainage difficult.
n. Positioning the unit on a floor area (terrace, land, roof, etc.) in areas that are difficult to access.
The support base must have good drainage of the water and prevent the possible accumulation of dirt
under the unit, (e.g. dry leaves - figure 13).
In this case, make a raised area of 10÷15 cm onto which the unit can be fixed using foundation studs.
No interventions are required when positioned on a balcony, since there is already enough slope for the
regular run-off of the water and sufficient protection from the accumulation of dirt.
o. Positioning the unit on a rigid metal base (brackets, metal profile supports, etc.).
In this case, the unit must always be fastened to the support base via vibration dampers (figure 14) with
dimensions and capacity suitable for the weight of the machine (on request).
Furthermore, the base must have appropriate rigidity to prevent the amplification of vibrations due to
regular operation.
p. Make sure that there is the minimum space around the outdoor unit necessary to guarantee correct
operation and the cleaning and maintenance interventions, as indicated in figure X3.
A
300
min.
300
mm
C
2000

2.6.1 - Heat pump appliances

• During operation in heating mode, condensate is produced in the outdoor unit due to defrosting, which
must be able to run-off freely to prevent stagnation.
• When positioned on a flat surface, a draining channel must be created around the unit that goes directly
into the rainwater collection well of the water network (figure 15).
• In the case of installation on a balcony or terrace, it must be possible to position a recipient under the
unit, possibly in galvanised sheet or stainless steel (preferable), with drain pipe that flows directly into the
gutter.
min.
mm
min.
600
mm
B
min.
mm
min. 600
min.
300
C
ARYAL S1 E INVERTER 10-12-18-24 C
X
3
D
mm
E
mm
A
F
EN - 13

Advertisement

Table of Contents
loading

Table of Contents