3 | Areas of application
3.3 Limits of application
Max. permissible operating pressure (LP/HP)
LP = Low pressure
1)
HP = High pressure
© Danfoss | Climate Solutions | 2023.07
Compressor operation is possible within the operating limits.
These can be found in Bock compressor selection tool (VAP)
under vap.bock.de. Observe the information given there.
- Permissible ambient temperature -4°F ... 140°F (-20 °C) - (+60 °C).
- Max. permissible discharge end temperature 320°F (160 °C).
- Min. discharge end temperature ≥ 122°F (50 °C).
- Min. oil temperature ≥ 86°F (30 °C).
- Max. permissible switching frequency 12x /h.
- A minimum running time of 3 min. steady-state condition
(continuous operation) must be achieved.
Avoid continuous operation in limit range.
For operation with frequency converter:
- Frequency range 30 - 70 Hz.
: 1450/1450 psig, 100/100 bar
1)
AQ450435396289en-US0201 | 9
D
US
Need help?
Do you have a question about the BOCK UL-HGX24e CO2 LT and is the answer not in the manual?