Toshiba RAV-SM2244DTP-TR Service Manual page 32

Table of Contents

Advertisement

No.
Item
9
High-temp.
release control
10
Drain pump
control
11
After-heat
elimination
Outline of specifications
1) The heating operation is performed as follows based on the
detected temperature of T
• When [M] zone is detected, the commanded frequency is
decreased. After then the commanded frequency changes
every 30 seconds while operation is performed in [M]
zone.
• In [N] zone, the commanded frequency is held.
• When [L] zone is detected, the commanded frequency is
returned to the original value by approx. 6Hz every
60 seconds.
Setup at shipment
Control temp. °C
A
B
56 (54)
52 (52)
NOTE:
When the operation has started or when T
operation start, the release temperature is controlled between
values in parentheses of A and B.
1) In cooling operation (including Dry operation), the drain
pump is usually operated.
2) If the float switch works while drain pump drives, the
compressor stops, the drain pump continues the operation,
and a check code is output.
3) If the float switch works while drain pump stops, the
compressor stops and the drain pump operates. If the float
switch keeps operating for approx. 4 minutes, a check code
is output.
When heating operation stops, in some cases, the indoor fan
operates with (L) for approx. 30 seconds.
sensor or T
sensor.
C
CJ
TC, TCJ
˚C
A
B
L
C
or T
CJ
– 32 –
However this control is
ignored in case of the
follower unit of the twin.
M
N
Same status as that
< 30°C after
when "thermostat-OFF"
(status that the air
conditioner enters in the
room temp. monitor
mode when the
temperature reached the
setup temperature on
the remote controller)
Check code [P10]
Drain pump kit
TCB-DP40DE
(Sold separately)
Remarks