Recommended wire routing of leadwires
Do not run high voltage ignition transformer wires in the same
conduit with the flame detector or data lines.
Be sure loads do not exceed the terminal ratings. Refer to the
labels or terminal ratings in Table 3.
The SLATE system must be mounted in an electrical enclosure.
When mounting in an electrical enclosure, provide adequate
clearance for servicing, installation and removal of SLATE
modules.
Maximum wire length:
• The maximum leadwire length is 300 feet to terminal inputs
(Control, Running/Lockout Interlock)
• For Remote Bus data lines, maximum cable length depends on
the number of modules connected, the noise conditions and
the cable used. The maximum of all interconnecting wires is
4000 feet.